PROGRAMMING THE OPERATIONAL LOGIC

It is possible for the control unit to use several different operational logic states, by simply moving the dip-switches located on the card.
The functions associated with each individual dip-switch are listed below.

DIP

FUNCTION

SETTING

DESCRIPTION

1

Pre-flashing

ON

Disabled

The blinker is switched on when the motor is started

OFF

Enabled

The blinker is switched on 2 seconds before the motor is started

2

Automatic
closure

ON

Enabled

The gate is closed automatically after the period of time set by the PAUSE
trimmer

OFF

Disabled

On completion of the opening step, the gate remains open. It is necessary to
instruct closure with another START command

3

Start opening

ON

Not accepted

Any START command issued during opening is not heard

OFF

Accepted

Any START command issued during opening is accepted

4

Operational logic

ON

Inversion

Start during opening causes closure. 
Start during closure causes opening.

OFF

Step

Commands subsequent to starting cause, in order: 
open 

쩚쩛

stop 

쩚쩛

close 

쩚쩛

stop...

5

Slow down

ON

Enabled

At the end of each opening and closing step, the motor slows down in order to
avoid noisy closure and bouncing.

WARNING: With gates that are particularly heavy, or with high friction,
breaking is not recommended, as it may lead to undesired stopping 

OFF

Disabled

6

Start off

ON

Disabled

At the start of each opening and closing step, the motor is started at maximum
power 

OFF

Enabled

7

Anti-slip

ON

Disabled

The time used for opening or closure will always be the value set by the WORK
trimmer, even if the previous operation has been interrupted before the expiry
of such time.

OFF

Enabled

When an opening (or closing) operation is interrupted before expiry of the set
time (for example due to the intervention of one of the safety devices or due to
a start command), the duration of the subsequent closing (or opening)
operation will not be that set by the WORK trimmer, but will be equal to the
time effectively elapsed, plus a short supplemental time in order to compensate
for the inertia of the gate.

8

Photocell

ON

Always active

Intervention of the photocell during opening or closing causes the gate to stop.
When the photocell restores, the gate re-opens completely.

OFF

NOT active during
opening:

Intervention of the photocell during opening is ignored. Intervention of the
photocell during closing causes the gate to be re-opened completely.

9

Photocell test

ON

Enabled

The control unit performs a photocell operational test before starting each
opening or closing operation. If the photocells are not operating correctly, the
gate does not begin to move and the light flashes for approx. 8 seconds.

PLEASE NOTE:  connect the photocell TX correctly

OFF

Disabled

10

Safety edge 
type

ON

Conductive rubber
edge

Select this option if using conductive rubber edges with nominal resistance of
8K2.

OFF

Standard or optical
edge

Select this option if using standard edges with switch normally closed or optical
edges.

11

Safety edge

ON

Always active

Intervention of the edge during opening or closing causes inversion of the
direction of movement in order to free the body that caused the edge to
intervene. The gate will be stopped after approx. 3 seconds.

OFF

NOT active during
opening:

Intervention of the edge during opening is ignored. Intervention of the edge
during closing causes the gate to re-open completely.

12

Safety edge test

ON

Enabled

The control unit performs an operational test on the edges before starting each
opening or closing operation. If the edges are not operating correctly, the gate
does not begin to move and the light flashes for approx. 8 seconds. 

DO NOT enable testing if conductive rubber edges are used or standard
edges are used without a suitable control unit for controlling function.

OFF

Disabled

Содержание City9

Страница 1: ...39 01 72 84 050 info v2home com www v2home com City9 CENTRALE DI COMANDO ANALOGICA PER CANCELLI SCORREVOLI ANALOGUE CONTROL UNIT FOR SLIDING GATES ARMOIRE DE COMMANDE ANALOGIQUE POUR PORTAILS COULISSA...

Страница 2: ......

Страница 3: ...CT RISTIQUES TECHNIQUES 13 TABLEAU BRANCHEMENTS ELECTRIQUES 14 R GLAGE DE LA PUISSANCE ET DES TEMPS DE TRAVAIL 15 INDICATEURS DELs SUR L ARMOIRE DE COMMANDE 15 MONTAGE DES PASSE C BLES 15 INSTALLATION...

Страница 4: ......

Страница 5: ...gato IIA E obbligo attenersi alle seguenti norme per chiusure veicolari automatizzate EN 12453 EN 12445 EN 12978 ed alle eventuali prescrizioni nazionali Anche l impianto elettrico a monte dell automa...

Страница 6: ...Alimentazione TX fotocellule per Test funzionale C1 Apertura motore C2 Comune motore C3 Chiusura motore D1 D2 Contatto per attivare il temporizzatore di una luce di cortesia D3 D4 Lampeggiante 230V 4...

Страница 7: ...chiuso ingresso STOP aperto PHOTO ingresso PHOTO chiuso ingresso PHOTO aperto EDGE Costa tradizionale Ingresso EDGE chiuso costa non schiacciata Ingresso EDGE aperto costa schiacciata Costa a gomma re...

Страница 8: ...i riaprir completamente 2 Fotocellula NON attiva in apertura L intervento della fotocellula durante l apertura viene ignorato L intervento della fotocellula durante la chiusura causa la riapertura com...

Страница 9: ...mandi di start pedonale funzioneranno secondo la logica passo passo Durante un ciclo pedonale il comando di start provoca l apertura completa del cancello Collegare i cavi del dispositivo che comanda...

Страница 10: ...ervento di una delle sicurezze o per un comando di start la durata della chiusura o apertura successiva non sar quella impostata con il trimmer WORK ma sar pari al tempo effettivamente trascorso pi un...

Страница 11: ...53 EN 12445 EN 12978 as well as any local rule in force Also the automation upstream electric system shall comply with the laws and rules in force and be carried out workmanlike The door thrust force...

Страница 12: ...ries L10 L11 Power supply for functional test TX photocell C1 Motor open C2 Motor common C3 Motor close D1 D2 Courtesy light timer activation switch D3 D4 230V 40W 120V 40W blinker N 230V 120V power s...

Страница 13: ...sed edge not pressed EDGE input open edge pressed Resistive rubber edge EDGE input closed edge pressed EDGE input open fault Edge NO pressed 8K2 between EDGE input and common FCA Opening limit switch...

Страница 14: ...pens completely 2 Photocell NOT active during opening Intervention of the photocell during opening is ignored Intervention of the photocell during closing causes the gate to re open completely Indepen...

Страница 15: ...strian cycle the start command causes the complete opening of the gate Connect the start input control device cables between terminals L4 and L8 on the control unit STOP The STOP input is intended for...

Страница 16: ...evices or due to a start command the duration of the subsequent closing or opening operation will not be that set by the WORK trimmer but will be equal to the time effectively elapsed plus a short sup...

Страница 17: ...EN 12978 et toutes ventuelles prescriptions nationales M me l installation lectrique ou on branche l automatisme doit r pondre aux normesen vigueur et tre fait r gles de l art La r gulation de la for...

Страница 18: ...le commun commandes COM Les entr es fin de course ouverture FCA A et fin de course fermeture FCC B si non utilis es doivent tre shunt es avec le commun fin de corse D J1 L1 Centrale antenne L2 Blindag...

Страница 19: ...aux dimensions du passe c ble Fixer les passe c bles avec les crous pr vus cet effet INDICATEURS DELs SUR L ARMOIRE DE COMMANDE Les cases mises en vidence indiquent la condition des DELs quand le por...

Страница 20: ...ellule pendant l ouverture est ignor e L intervention de la photocellule pendant la fermeture cause la r ouverture compl te du portail Ind pendamment de la configuration choisie quand le portail est o...

Страница 21: ...cause l ouverture partielle environ la moiti de la course du portail Des commandes successives de start pi tonnier fonctionneront selon la logique pas pas Pendant un cycle pi tonnier la commande de st...

Страница 22: ...le trimmer WORK mais sera gale au temps effectivement pass plus un bref temps additionnel pour compenser l inertie du portail en phase d arr t 8 Photocellule ON Active toujours L intervention de la p...

Страница 23: ...53 EN 12445 EN 12978 y a las eventuales prescripciones nacionales Incluso la instalaci n el ctrica antes de la automatizaci n debe responder a las vigentes normativas y estar realizada correctamente L...

Страница 24: ...Alimentaci n de la fotoc lula de TX para la prueba funcional C1 Apertura motor C2 Com n motor C3 Cierre motor D1 D2 Contacto para activar el temporizador de una luz de cortes a D3 D4 Intermitente 230V...

Страница 25: ...c bles est indiqu dans la figure ATTENTION Avant de percer le bo tier d monter la carte lectronique Percer le bo tier avec une fraise ad quate par rapport aux dimensions du passe c ble Fixer les passe...

Страница 26: ...va en la apertura Se ignora la intervenci n de la fotoc lula durante la apertura La intervenci n de la fotoc lula durante el cierre causa la reapertura completa de la cancela Independientemente de la...

Страница 27: ...comandos peatonales sucesivos de inicio funcionan seg n la l gica paso a paso Durante un ciclo peatonal el comando de inicio provoca la apertura completa de la cancela Conecte los cables del dispositi...

Страница 28: ...n comando de inicio la duraci n del cierre o apertura sucesiva no ser la programada por el potenci metro de ajuste WORK sino que ser igual al tiempo efectivamente transcurrido m s un breve tiempo adic...

Страница 29: ...eventuais prescri es nacionais A instala o a montante da automa o tamb m deve respeitar as normas vigentes e ser realizadas conforme as regras da arte A regula o da for a de impulso da folha deve med...

Страница 30: ...0 L11 Alimenta o TX c lulas fotoel ctricas para Teste funcional C1 Abertura motor C2 Comum motor C3 Fechadura motor D1 D2 Contacto para activar o temporizador de uma luz de cortesia D3 D4 Pisca pisca...

Страница 31: ...o costa n o esmagada Ingresso EDGE aberto costa esmagada Costa de borracha resist vel Ingresso EDGE fechado costa esmagada Ingresso EDGE aberto anomalia Costa N O esmagada 8K2 entre ingresso EDGE e co...

Страница 32: ...se completamente 2 C lula fotoel ctrica N O activa na abertura A interven o da c lula fotoel ctrica durante a abertura ignorada A interven o da c lula fotoel ctrica durante a fechadura provoca a reabe...

Страница 33: ...ndos de start de pedestre funcionar o consoante a l gica passo a passo Durante um ciclo de pedestre o comando de start provoca a abertura completa do port o Conectar os cabos do dispositivo que comand...

Страница 34: ...de start a dura o da fechadura ou abertura sucessiva n o ser aquela configurada com o trimmer WORK mas ser igual ao tempo efectivamente passado mais um breve tempo acrescido para compensar a in rcia...

Страница 35: ......

Страница 36: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2home com www v2home com...

Отзывы: