INSTALLATION

Installation of the control unit, the safety devices and accessories
must be performed with the power supply disconnected.

POWER SUPPLY

The control unit must be powered by means of a 230 V - 50 Hz
or 120 V - 60 Hz power line, depending on the model, protected
by a differential magnetothermal switch in compliance with legal
regulations. 
Connect the power cables to the control unit 

L

and 

N

terminals.

MOTOR

The control unit can control one asynchronous AC motor. 

Connect the cables for motor as follows:
• Opening cable to terminal 

C1

• Closing cable to terminal 

C3

• Common return cable to terminal 

C2

• Start-up capacitor between terminals 

C1

and 

C3

BLINKER

The control unit provides for the use of a 230 V - 40 W or 120 V
- 40 W blinker with built-in intermittence. 
Connect the cables to terminals 

D3

and 

D4

.

COURTESY LIGHT

This output has a normally-open clean contact relay which closes
for approx. 1 second at the start of an opening phase. This
switch may be used to activate a courtesy light timer (max. load: 
230V - 4A).

PLEASE NOTE:

If there is no timer, the courtesy light can be

controlled using channel 4 of receiver MR1: bistable or timer
programmable channel (read the instructions for the receiver MR1
thoroughly).

The switch is on terminals 

D1

and 

D2

.

PHOTOCELLS

The control unit has a 24VAC power supply for photocells with
switch normally closed, and can perform an operational test
before starting the gate opening procedure. 

The photocell can be used with two settings:

1. Photocell always active: 

Intervention of the photocell during opening or closing 
causes the gate to stop.
When the photocell restores, the gate re-opens completely.

2. Photocell NOT active during opening: 

Intervention of the photocell during opening is ignored.
Intervention of the photocell during closing causes the gate 
to re-open completely.

Independently of the setting selected, when the gate is paused
while opening, the time count for any automatic re-closure will
only start after the photocell restores.

• Connect the photocell transmitter power cables between 

terminals 

L10

(GND) and 

L11

(+) on the control unit.

• Connect the photocell receiver power cables between 

terminals 

L10

(GND) and 

L9

(+) on the control unit.

• Connect the photocell receiver output between terminals 

L6

and 

L8 

on the control unit.

SAFETY EDGES

The control unit has an input for controlling safety edges; this
input is capable of controlling standard edges with switch
normally closed and conductive rubber edges with nominal
resistance of 8.2 kOhms.

Edges can be used with two settings:

1. Edge always active: 

Intervention of the edge during opening or closing causes 
inversion of the direction of movement in order to free the 
body that caused the edge to intervene. 
The gate stops after approx. 3 seconds.

2. Edge NOT active during opening:

Intervention of the edge during opening is ignored.
Intervention of the edge during closing causes the gate 
re-open completely.

Independently of the settings selected, any subsequent automatic
re-closure will be cancelled.

Standard edge with switch normally closed: 

connect the

edge cables between terminals 

L7

and 

L8

on the control unit.

In order to satisfy the requirements of standard EN12978, it is
necessary to install safety edges with a control unit which
constantly monitors correct operation. If control units are used
with the option of running tests by means of interrupting the
power supply, connect the control unit power supply cables
between terminals 

L10

(GND) and 

L11

(+). 

Содержание City9

Страница 1: ...39 01 72 84 050 info v2home com www v2home com City9 CENTRALE DI COMANDO ANALOGICA PER CANCELLI SCORREVOLI ANALOGUE CONTROL UNIT FOR SLIDING GATES ARMOIRE DE COMMANDE ANALOGIQUE POUR PORTAILS COULISSA...

Страница 2: ......

Страница 3: ...CT RISTIQUES TECHNIQUES 13 TABLEAU BRANCHEMENTS ELECTRIQUES 14 R GLAGE DE LA PUISSANCE ET DES TEMPS DE TRAVAIL 15 INDICATEURS DELs SUR L ARMOIRE DE COMMANDE 15 MONTAGE DES PASSE C BLES 15 INSTALLATION...

Страница 4: ......

Страница 5: ...gato IIA E obbligo attenersi alle seguenti norme per chiusure veicolari automatizzate EN 12453 EN 12445 EN 12978 ed alle eventuali prescrizioni nazionali Anche l impianto elettrico a monte dell automa...

Страница 6: ...Alimentazione TX fotocellule per Test funzionale C1 Apertura motore C2 Comune motore C3 Chiusura motore D1 D2 Contatto per attivare il temporizzatore di una luce di cortesia D3 D4 Lampeggiante 230V 4...

Страница 7: ...chiuso ingresso STOP aperto PHOTO ingresso PHOTO chiuso ingresso PHOTO aperto EDGE Costa tradizionale Ingresso EDGE chiuso costa non schiacciata Ingresso EDGE aperto costa schiacciata Costa a gomma re...

Страница 8: ...i riaprir completamente 2 Fotocellula NON attiva in apertura L intervento della fotocellula durante l apertura viene ignorato L intervento della fotocellula durante la chiusura causa la riapertura com...

Страница 9: ...mandi di start pedonale funzioneranno secondo la logica passo passo Durante un ciclo pedonale il comando di start provoca l apertura completa del cancello Collegare i cavi del dispositivo che comanda...

Страница 10: ...ervento di una delle sicurezze o per un comando di start la durata della chiusura o apertura successiva non sar quella impostata con il trimmer WORK ma sar pari al tempo effettivamente trascorso pi un...

Страница 11: ...53 EN 12445 EN 12978 as well as any local rule in force Also the automation upstream electric system shall comply with the laws and rules in force and be carried out workmanlike The door thrust force...

Страница 12: ...ries L10 L11 Power supply for functional test TX photocell C1 Motor open C2 Motor common C3 Motor close D1 D2 Courtesy light timer activation switch D3 D4 230V 40W 120V 40W blinker N 230V 120V power s...

Страница 13: ...sed edge not pressed EDGE input open edge pressed Resistive rubber edge EDGE input closed edge pressed EDGE input open fault Edge NO pressed 8K2 between EDGE input and common FCA Opening limit switch...

Страница 14: ...pens completely 2 Photocell NOT active during opening Intervention of the photocell during opening is ignored Intervention of the photocell during closing causes the gate to re open completely Indepen...

Страница 15: ...strian cycle the start command causes the complete opening of the gate Connect the start input control device cables between terminals L4 and L8 on the control unit STOP The STOP input is intended for...

Страница 16: ...evices or due to a start command the duration of the subsequent closing or opening operation will not be that set by the WORK trimmer but will be equal to the time effectively elapsed plus a short sup...

Страница 17: ...EN 12978 et toutes ventuelles prescriptions nationales M me l installation lectrique ou on branche l automatisme doit r pondre aux normesen vigueur et tre fait r gles de l art La r gulation de la for...

Страница 18: ...le commun commandes COM Les entr es fin de course ouverture FCA A et fin de course fermeture FCC B si non utilis es doivent tre shunt es avec le commun fin de corse D J1 L1 Centrale antenne L2 Blindag...

Страница 19: ...aux dimensions du passe c ble Fixer les passe c bles avec les crous pr vus cet effet INDICATEURS DELs SUR L ARMOIRE DE COMMANDE Les cases mises en vidence indiquent la condition des DELs quand le por...

Страница 20: ...ellule pendant l ouverture est ignor e L intervention de la photocellule pendant la fermeture cause la r ouverture compl te du portail Ind pendamment de la configuration choisie quand le portail est o...

Страница 21: ...cause l ouverture partielle environ la moiti de la course du portail Des commandes successives de start pi tonnier fonctionneront selon la logique pas pas Pendant un cycle pi tonnier la commande de st...

Страница 22: ...le trimmer WORK mais sera gale au temps effectivement pass plus un bref temps additionnel pour compenser l inertie du portail en phase d arr t 8 Photocellule ON Active toujours L intervention de la p...

Страница 23: ...53 EN 12445 EN 12978 y a las eventuales prescripciones nacionales Incluso la instalaci n el ctrica antes de la automatizaci n debe responder a las vigentes normativas y estar realizada correctamente L...

Страница 24: ...Alimentaci n de la fotoc lula de TX para la prueba funcional C1 Apertura motor C2 Com n motor C3 Cierre motor D1 D2 Contacto para activar el temporizador de una luz de cortes a D3 D4 Intermitente 230V...

Страница 25: ...c bles est indiqu dans la figure ATTENTION Avant de percer le bo tier d monter la carte lectronique Percer le bo tier avec une fraise ad quate par rapport aux dimensions du passe c ble Fixer les passe...

Страница 26: ...va en la apertura Se ignora la intervenci n de la fotoc lula durante la apertura La intervenci n de la fotoc lula durante el cierre causa la reapertura completa de la cancela Independientemente de la...

Страница 27: ...comandos peatonales sucesivos de inicio funcionan seg n la l gica paso a paso Durante un ciclo peatonal el comando de inicio provoca la apertura completa de la cancela Conecte los cables del dispositi...

Страница 28: ...n comando de inicio la duraci n del cierre o apertura sucesiva no ser la programada por el potenci metro de ajuste WORK sino que ser igual al tiempo efectivamente transcurrido m s un breve tiempo adic...

Страница 29: ...eventuais prescri es nacionais A instala o a montante da automa o tamb m deve respeitar as normas vigentes e ser realizadas conforme as regras da arte A regula o da for a de impulso da folha deve med...

Страница 30: ...0 L11 Alimenta o TX c lulas fotoel ctricas para Teste funcional C1 Abertura motor C2 Comum motor C3 Fechadura motor D1 D2 Contacto para activar o temporizador de uma luz de cortesia D3 D4 Pisca pisca...

Страница 31: ...o costa n o esmagada Ingresso EDGE aberto costa esmagada Costa de borracha resist vel Ingresso EDGE fechado costa esmagada Ingresso EDGE aberto anomalia Costa N O esmagada 8K2 entre ingresso EDGE e co...

Страница 32: ...se completamente 2 C lula fotoel ctrica N O activa na abertura A interven o da c lula fotoel ctrica durante a abertura ignorada A interven o da c lula fotoel ctrica durante a fechadura provoca a reabe...

Страница 33: ...ndos de start de pedestre funcionar o consoante a l gica passo a passo Durante um ciclo de pedestre o comando de start provoca a abertura completa do port o Conectar os cabos do dispositivo que comand...

Страница 34: ...de start a dura o da fechadura ou abertura sucessiva n o ser aquela configurada com o trimmer WORK mas ser igual ao tempo efectivamente passado mais um breve tempo acrescido para compensar a in rcia...

Страница 35: ......

Страница 36: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2home com www v2home com...

Отзывы: