CALL MODULES
PROGRAMMING
10
3. EI/OC/DOOR/PS CONFIGURATION
3.01 FREQUENCY OF ELECTRICAL LOCK
P 3. 0 1
In this step we can set frequency of electrical lock which is attached
to
+C –C
terminals in keyboard. This output can support DC and AC
electrical locks. This parameter determines the voltage frequency
on
+C –C
terminals
.
Below table presents electrical lock frequencies:
Parameter Frequency
0 DC
1 500Hz
2 250Hz
3 166Hz
4 125Hz
5 100Hz
6 83Hz
7 71Hz
8 62Hz
9 55Hz
10 50Hz
11 45Hz
12 41Hz
13 38Hz
14 35Hz
15 33Hz
16 31Hz
17 29Hz
18 27Hz
19 26Hz
20 25Hz
Press and hold
#
button to save value.
Default setting
-
0
3.02 DC TIME DURING ELECTRICAL LOCK RELEASE
P 3. 0 2
Just after releasing electrical lock there is DC flowing in it. After
specified time the current changes to AC.
After pressing
#
button actual time expressed in milliseconds will be
displayed.
Press shortly
#
button to leave this parameter unchanged or enter
new value within 0 – 250 milliseconds range.
Press and hold
#
button to save value.
Default setting
-
200
3.03 ELECTRICAL LOCK CURRENT
P 3. 0 3
In this step we can set the value of the current of the electrical lock.
When we set this parameter to 10 then through electrical lock flows
the lowest current (360 mA*). But when we set to 90 (max value)
then through the electrical lock flows the highest current (750 mA*).
After pressing
#
button actual value expressed in % will be
displayed.
Press shortly
#
button to leave this parameter unchanged or enter
new value within 10 – 90 range.
Press and hold
#
button to save value.
Default setting
-
30
* During current measurement to the C+ and C- lines there were
attached electrical lock BIRATRONIK 8-12V AC, 300 mA powered
with DC.
3.04 ELECTRICAL LOCK MODE
P 3. 0 4
In this step we can set electrical lock mode.
The options are:
0
Normal,
1
Reverse
(only DC). In this mode to the oC –C shouldn’t
be directly connected electromagnetic lock. It can damage the
call module.
Press and hold
#
button to save value.
Default setting
-
0
3.05 ELECTRICAL LOCK RELEASE
P 3. 0 5
In this step we can set electrical lock release in dependence on
event. The electrical lock will be released after event occurs or after
specified event duration. Depending on the parameter value we
have following options:
0
Electrical lock is disabled,
1
Time activation / releasing impulse after pressing T1 button in
handset (180R)
4
After entering individual opening code preceded with double
press
#
button,
8
After entering individual opening code preceded with single
press
#
button, Dallas key or DOOR button (on handset),
16
Activation with EI4 input (after connecting EI4 with GND),
32
Activation with EI3 input (after connecting EI3 with GND),
64
Activation with EI2 input (after connecting EI2 with GND),
128
Activation with EI1 input (after connecting EI1 with GND).
NOTE: If we need that electrical lock was opened by several
events then parameters should be added together, for example
after connecting EI1 with GND and entering individual opening
codes. We should add values for these events (8+128=136) and
enter this value in this step.
Press and hold
#
button to save value.
Default setting
-
8
3.06 SETTING EI1 AS A DIRECT CALL
P 3. 0 6
In this step we can assign to EI1 input a function of a direct call of
specified doorphone. This can be useful if, beside numeric
keyboard, we need to install keyboard with function buttons. After
setting doorphone’s address (1-255 range) and connecting EI1
input with GND then doorphone with specified address will be
called.
In this step we can set electrical lock work mode. The options are:
0
Disabled (it is controlled with steps 3.05, 3.10 and 3.11
settings),
1-255
Direct call (this number mean physical address).
Press and hold
#
button to save value.
Default setting
-
0