User and
installation guide
Uponor Comfort E thermostat dig.prog.
flush Set T-87IF 230V
468 931 004 254-02
t
1 Principle of operation
The programmable temperature controller T-87IF allows
programming switching events (up to 9) and temperatures
according to personal needs. After installation the device auto-
matically shows the time of day and the room temperature. In
AUTO mode, the heater will be automatically activated accor-
ding to programmed time and temperature. Program 1 is the
default pre-set program (see 8.).
Room temperature will be controlled, the floor temperature will
be limited (measured by the remote sensor). The heater will be
switched on when the temperature drops below the current
set-point.
In case of function „Min Floor Temp“ (H3) it will be heated if the
floor temp drops below the set min-value. This is even when the
room temp. is too high.
In case of function „Max Floor Temp“ (H3) heating will be stop-
ped if the floor temp exceeds the set max-value. This is even
when the room temp. is too low.
2 Installation
Caution!
This device must be installed by a qualified electrician,
according to the wiring diagram on the device and in com-
pliance with all applicable safety regulations.
Appropriate installation measures must be taken to achieve
the requirements of protection class II.
This device, is used to control the temperature only in
dry rooms, under normal environmental conditions. This
electronic device conforms to EN 60730, It is an “indepen-
dently mounted control” and works according to operating
principle 1C.
3 Use
The electronic Room Temperature Controller T-87IF can be used
to control the room temperature in conjunction with:
• Electrical floor heating systems where the floor temperature
has to be limited to a certain value
• Hot-water floor heating systems in conjunction with
thermal actuators
In order to measure the floor temperature the remote
sensor has to be used
4 Features
• One line text display for simplified operation
• Back light
• Real time clock (setting of year, month, day, time)
• Automatic Summer- Winter time change over
• Max 9 events per day (each day independently)
• Pre-set and adjustable programs
• Optimum-Start
• Arm chair programming (with display unit removed)
• OFF-Function, Key V to be pressed for 10 sec
• Holiday-Mode (date from - until can be set)
• Timer (Party) specific temperature for configurable duration
• Energy consumption display (heating on time * cost) for last 2
days, -week, -month, -year
• Energy cost per hour configurable
• Frost protection
• Range limits for adjusting max and min temperature
• Access protection
• Operating language can be selected
• Control mode PWM or ON/OFF
• Minimum output on/off time and hysteresis configurable for
ON/OFF control
Remote Sensor
20
Ø7,8
8. Pre-set programs
There are 3 pre-set time/temperature programs in the controller.
Pre-set program 1 (as shown below) is the default. Therefore, if
pre-set program 1 is the best program to suit the application,
there will be no need to change the time/temperature settings
on the device.
To select another program see 9. G1.
Program 1
Monday to Friday
Events
1
2
3
4
5
6
Time
6:00
8:30
12:00 14:00 17:00
22:00
Temperature °C
21,0
18,0
21,0
18,0
21,0
15,0
Saturday and Sunday
Events
1
2
3
4
5
6
Time
7:00
10:00 12:00 14:00 17:00 23:00/22:00*
Temperature °C
21,0
18,0
21,0
21,0
21,0
15,0
6:00 h
8:00 h
10:00 h
12:00 h
14:00 h
16:00 h
18:00 h
20:00 h
22:00 h
Mon – Fri
Sat – Sun
*23:00/22:00 = 23:00 for Saturday
Program 2
Monday to Friday
Events
1
2
3
4
5
6
Time
6:00
8:30
12:00 14:00 17:00
22:00
Temperature °C
21,0
18,0
21,0
18,0
21,0
15,0
Saturday and Sunday
Events
1
2
Time
7:00
23:00/22:00*
Temperature °C
21,0
15,0
6:00 h
8:00 h
10:00 h
12:00 h
14:00 h
16:00 h
18:00 h
20:00 h
22:00 h
Mon – Fri
Sat – Sun
*23:00/22:00 = 23:00 for Saturday
Program 3
Monday to Friday
Events
1
2
5
6
Time
6:00
8:30
17:00
22:00
Temperature °C
21,0
18,0
21,0
15,0
Saturday and Sunday
Events
1
2
3
4
Time
7:00
10:00
12:00 23:00/22:00*
Temperature °C
21,0
18,0
21,0
15,0
6:00 h
8:00 h
10:00 h
12:00 h
14:00 h
16:00 h
18:00 h
20:00 h
22:00 h
Mon – Fri
Sat – Sun
*23:00/22:00 = 23:00 for Saturday
Notes for Programming
• Activated settings terminate automatically 3 Min after the last
key press, without saving. They return to the mode which was
active before entering the settings, e.g. AUTO, MAN, etc.
• Entering a Code: change value with
+ –
key then press OK
• When going through User- or Installer settings the item num-
ber used in the manual will be displayed, e.g. G1 for „Program
select one“ or H2 for „Control Mode“.
• There may be gaps in the sequence of menu numbers.
Troubleshooting
1. It is getting warm too late:
a. Are clock and program events set correctly?
b. Is the Optimum Start feature switched on? see H7
Did the controller have enough time (several days) to
adapt to the room’s characteristics?
c. Is an automatic change between Summer- and Winter
time activated, see G5
2. The controller does not accept any changes
Is access protection switched on? see G6
3. The range of temperature setting is limited.
Are temperature limits set? See G7
4. Temperature display doesn‘t change.
Is display of set-temperature activated? See G10
5. The room heats up too slow
The floor temperature may be limited from the
controller‘s max-limiter. See H3
6. The room becomes too warm
The floor temperature may be limited from the
controller‘s Min-limiter. See H3
• Min- and max limits for floor temperature adjustable
• Valve protection
• Adaptation to valves normally open or normally closed
• Adjustable heating interrupt according standard EN 50559
(not for valves normally open)
Electric connection
Caution:
disconnect electric circuit from supply
Connecting according to Wiring Diagram
For flexible or solid wires 1 - 2,5 mm2
Connecting the remote sensor
The T-87IF needs a remote temperature sensor. This sensor
should be mounted in such a way that the temperature which
has to be controlled, can be measured correctly. Lay sensor insi-
de a protective tube (simplifies replacement). The sensor lead
can be extended up to 50 m by using a cable and connections
suitable for 230 V. Avoid laying sensor cable alongside power
cables, for example inside a conduit.
Caution!
The sensor is at mains voltage.
6 Technical Data
Order Type
T-87IF
Supply voltage
230 V AC 50 HZ (207 … 253 V)
Temperature setting range
5 °C … 30 °C; in 0,5 °C steps
Temperature resolution
0,1°C steps
Output
Relay NO contact
Switching current
10mA … 12,5(4)A AC; 230 V~
Output signal
PWM (Pulse Width modulation)
or ON/OFF
PWM cycle time
adjustable
Hysteresis
adjustable (ON/OFF only)
Minimum programmable time
10 Min
Power consumption
~ 1,2 W
Accuracy of clock
< 4 Min / year
Power reserve
~ 10 Years
Remote sensor
length 4 m, can be extended
up to 50 m
Ambient temperature
Operating
Storage
without condensation
0 °C … 40 °C
–20 °C … 70 °C
Rated impulse voltage
4 kV
Ball pressure test
75 ± 2 °C
Voltage and Current for the
purposes of Interference mea-
surements
230 V, 0,1 A
Degree of protection
IP 30
Protection class of housing
II (see Caution)
Pollution degree
2
Software class
A
Weight (with remote sensor)
~ 280 g
Energy class
(acc. EU 811/2013, 812/2013,
813/2013, 814/2013)
IV = 2 %
7 Wiring Diagram / Dimensions
Sensor
L
N
N
230V~ 50Hz
L
N
Load
Actual Day
Actual
Room
Temperature
Calling for
Heat (Blinks if
detached from
power module
or there is no
mains power)
Helping text
Mode = AUTO
Time = 14:31
The controller should be mounted at a location in the room which:
• can be easily accessed
• is free of curtains, cabinets, shelves, etc.
• allows free air circulation
• is not exposed to direct sunlight
• is not draughty (when doors or windows are opened)
• is not directly influenced by the source of heat
• is not located on an outer wall
• is approx. 1.5 m above the floor.
Fitting
in a conduit box Ø 60 mm
• remove the display unit
• remove the frame
• Mount it following the reverse
procedure
Caution!
Mounting in plastic wall boxes only
5. Mounting
To insert or remove a
flexible wire press pin
The plastic tab must be in place to provide insulation
between the terminals/wires and the mounting screw.
Caution!
Maximum length
of removed cable
insulation 8 mm.
9 Description of Functions and Operation
Selecting languages
Only for products where no language is pre-set, user has to set up his language by doing this:
ENGLISH
+ –
to select language
(This input is only requested at first start or Reset)
2 x OK
to accept -> AUTO will be displayed (to change language
again use menu G14)
How the T-87IF Temperature Controller can be used
Change temperature until next switching event
see keys, + – in AUTO
Set temperature for a number of hours
see main menu, TIMER
Adjust the controller to personal needs
see main menu, USER-SETTINGS
Controlling the temperature according to pre-set profiles
see main menu, AUTO
Set temperature for a specific date
see main menu, HOLIDAY
Adjust the controller to application needs
see main menu, INSTALLER-SETTINGS
Set a constant temperature (manual operation)
see main menu, MAN
Use a separate program for special days
see main menu, AT-HOME
Keys
to confirm / activate
+ – in AUTO (-)
Set temperature temporarily until next switching event. Indicated by „-“ behind AUTO-. First key-press shows set value, following ones change it.
OK
+ – in menu
Scroll through the menu
OK
Accepts modification / selection
Info
Show related details in AUTO, MAN, TIMER, HOLIDAY, AT-HOME. To cancel press key again
Menu
Enter menus. + – Key to move
V
Go one step back
V
for 10 sec
Switch off connected load. Display shows OFF. Details see G4
Main Menu
to confirm / activate
A
MENU
Use + – in order to navigate through the menu
B
AUTO
The temperature will be controlled automatically according to the time and temperature of the selected program, see G1. Use + – keys to change temperature
until next switching event.
OK
C
MAN
The temperature will be controlled continuously according to the temperature set in this menu. Use + – key to change temperature.
OK
D
TIMER
The temperature will be controlled temporarily according to the hours and temperature set in this menu. On terminating TIMER mode, the previously active
mode will be re-activated. Holiday terminates Timer.
OK
E
HOLIDAY
The temperature will be controlled between the dates and the temperature set in this menu. Holiday starts at 0h of the first day, it ends at 24h of the last day.
In the period of time before HOL starts, AUTO will be active. While waiting for holiday start date, other mode can be selected (AUTO, MAN, TIMER, HOME). INFO
provides details of the pending holiday. In this situation holiday period will start automatically when the DATE FROM occurs. When holiday ends it returns to the
mode which was in place before activating holiday.
OK
F
AT HOME
The temperature will be controlled automatically according to the time and temperature of the program configured here (independent from AUTO). The pro-
gram is the same for all days. Monday‘s program is used as the pre-set. It needs to be terminated by user, e.g, by selecting AUTO. Usage: for holiday at home,
illness etc.
OK
G
USER SETTINGS
Customise the controller according to personal requirements
OK
H
INSTALLER SETTINGS
Customise the controller according to application requirements (from installer only)
OK
G
USER SETTINGS
Customise the controller according to personal requirements
default settings
( ) = value range
1
Program select
Select one of the pre-defined programs, see 8. (If another program is chosen, settings will not be saved)
P1 (P … P3)
2
Event Setting
Modify Time and Temperature of active program, see 8. Each event can be reduced to the previous one or to 00:00h. Each event can be extended up to 23:50h,
then
->>> is indicating that the event is in the next day. By pressing + or – key at ->>> a time can be adjusted. Max 9 events are possible. The first digit indicates the
actual event e.g. 3.12:00- 14:00 shows event 3. Events can be set for day-blocks as well, when selecting days (Mon...Fri, Sat/Sun, Mon...Sun). In order to finish pro-
gramming, press
V
repeatedly.
as selected at G1
3
Clock Settings
Set Date and Time
4
Off Heating Permanent
Switch off the heater, the controller remains on power. Display reading OFF. Frost protection may happen if selected. See H6. Switching ON again by activating
e.g. AUTO or by pressing key
V
for 10 Sec. When re-activating via key
V
or this menu, AUTO will be activated.
NO
5
Summer/Winter time
change over
Select if automatic Summer/Winter-Time changeover
YES
6
Key Lock
Protect controller against unauthorised use. Re-activate via code = 93
NO
7
Temperature limits
min/max
Limits the temperature which can be set by the user, If both values are the same, no adjustment is possible. This affects AUTO, MAN, HOL, TIMER, AT-HOME,
event setting (G2). The active program / mode will not be affected automatically.
5; 30 °C
8
Cost/Hr for Energy
The assumed energy cost per hour (in cent/h) can be set. To use this feature as hour counter set the cost to 100 cent/h.
100 (1 … 999)
9
Energy consumption
to date
Shows the approximate energy cost of the controlled area. For the last: 2 days, week (7 days), month (30 days), year (365 days). On the actual day, calculation is
up to current time. In case of overflow 9999 will be displayed. This feature mainly can be used for electric heating.
Calculation: On-Time of heater x cost per hour see above. Reset see H9
10
Set temperature to read
Show set temperature instead of room temperature
NO
11
Adjust Temperature
Adjust temperature to personal needs
0.0 (-5.0 … +5.0)
13
Backlight
Continuously OFF or temporarily illuminates after key press
SHORT
(SHORT, OFF)
14
Language
Select preferred operating language
15
Info
Displays Controller-type and -version.
16
Reset user settings
only
Only USER SETTINGS will be set to factory settings. The energy counter will not be re-set; to do this see H9).
NO
Change INSTALLER SETTINGS
CAUTION!
These settings should only be set-up by a qualified person. They can influence safety and the proper functioning of the system.
H
INSTALLER SETTINGS
Customise the controller according application needs (by installer only)
default settings
( ) = value range
0
Code
Enter Code (= 7) in order to access the menus. It is valid for 1 Hour
1
Application
This controller is suitable for the heating system mentioned on right column.
LIMITER see 1.
2
Control Mode
PWM or ON/OFF can be selected. In case of PWM, the cycle time can be set (in Minutes). Min ON/OFF time = 10% of cycle time.
Use short time for fast and longer time for slow reacting heating systems.
For ON/OFF you can select:
• Hysteresis (OFF = no temperature hysteresis, even at very low changes of temp. the relay will switch over according to the Min On/Off Time setting.)
• Min On/Off Time (the minimum duration for the relay to be On or Off)
PWM/10 (/10 … 30)
OFF (OFF, 0.1 … 5.0)
10 Min
(1 … 30)
3
Min/max Floor
Temperature
Limits the floor temperature. Selectable is:
• Minimum floor temperature, the floor gets no colder as this temp. (OFF = no limit); e.g. Min-Temp. = 21°, the floor will get no colder than 21° even if the room is too warm
• Maximum floor temperature, the floor gets no warmer as this temp. (OFF = no limit); e.g. Max-temp. = 35°, the floor will get no warmer than 35°, even if the room is too cold
If one of these limits is not needed it should be set to OFF
OFF
(OFF, 10 … Tmax)
35 °C
(OFF, Tmin … 40)
5
Valve protection
The output will be activated for the specified time each day at 10:00 h in the morning
3 min (OFF, 1 … 10)
6
Frost protection
Set frost protection temperature. Only if controller is switched OFF, the temperature will be controlled to that value.
5 °C (OFF, 5 … 30)
7
Optimum Start
The set temperature will be reached at the time specified in the program. During pre-heating time, AUTO_ will be displayed
YES
8
Valves NO
If valves normally open have to be used
NO
9
Energy Counter Reset
The energy counter will be set to 0
NO
10
Display of
floor temperature
The temperature measured from remote sensor will be displayed (for service purpose)
Temperature
11
Reset all
All INSTALLER and USER settings will be set to its Factory setting
NO
12
EN 50559 Interrupt
Interrupts heating after continous heating of 1hr for this adjusted time
5 Min (0 … 20 Min)
10. Error Indication
In case of errors, „Err“ is blinking. The following errors can be displayed:
CONFIGURATION
Display- and powermodule do not fit
g
use only suitable parts
g
switch off and on power supplyge
EXT SENSOR
1. Error of remote sensor
g
replace sensor
2. Over- or under run of valid display ran
COMMUNICATION
Communication between display- and power unit fails
g
unplug and re-plug display unit
g
switch off and on power supply
On all these errors, heating will be activated with 30 % of time
11. Resistance values for remote sensor
Temperature
Resistance
Temperature
Resistance
10 °C
66,8 kΩ
30 °C
26,3 kΩ
20 °C
41,3 kΩ
40 °C
17,0 kΩ
25 °C
33 kΩ
50 °C
11,3 kΩ
t
*