ÜKY/DUO Boiler User Manual 

 

TRANSPORT AND SHIPPING 

 
ÜNMAK ÜKY/DUO series boilers are manufactured from welded thick sheet metal. 

1.

 

Boiler Group: Boiler insulation and outer jacket are shipped dressed. 

2.

 

Accessories: Control panel, pump (pump is given for capacities below 60.000 kcal/h power), 
warranty manual and boiler accessories are included in the boiler package.  

Safe transportation of the product 
Solid fuel boilers are heavy products, so care should be taken when moving the boiler to the place 
where  it  will  be  installed.  Therefore,  the  equipment  to  be  used  to  lift  and  transport  the  product 
should be at a sufficient capacity. 
In  order  not  to  damage  the  boiler  outer 
sheets 

and 

the 

boiler 

during 

transportation; 
 
In  small  boilers,  while  carrying  the 
transportation  rope  through  the  forklift 
stands  on  the  chassis  and  carrying  the 
boiler  with  the  help  of  a  crane  or  hoist, 
care  should  be  taken  not  to  damage  the 
painted thin sheets of the boiler and the reducer-fan group under the bunker. 
 
In  large  boilers,  it  is  also  suitable  to  be  lifted  from  the  forklift  stands  or  the  transport  ring  on  the 
boiler. If the connecting ropes are to be passed under the boiler while lifting with a crane, preventive 
measures should be taken to crush the upper tar of the boiler by the ropes. The boiler standing on 
the ground must be lifted directly without a puller. When carrying in cold weather, the boiler should 
not be lifted suddenly in case the rope freezes from the cold. 
 
 
 
 
 
 
 
 
 
 
 

 

Care should be taken not to damage the gearbox and fan under the bunker. 

 

When removing the packaging around the boiler, hard and cutting objects should not 
be used in order to prevent damage to the painted boiler plates underneath the 
packaging. 

 
 

Содержание UKY/DUO 100

Страница 1: ...KY DUO Boiler User Manual NL SOY Yap Malzemeleri Sanayi ve Ticaret Ltd ti Pancar Organize Sanayi B lgesi 2 Etap No 2 Torbal ZM R Tel 444 35 32 Faks 0232 469 2412 www unmak com...

Страница 2: ...ONS 6 ELECTRICAL INSTALLATION INSTRUCTIONS 8 INFORMATION ABOUT COMBUSTION 10 BOILER FEATURES 12 RULES FOR HEATING INSTALLATION 15 CONTROL PANEL AND USER INTERFACE 19 STARTING UP 21 FUEL FEEDING STAND...

Страница 3: ...re used only for heating installations not directly for domestic water heating However it can produce hot tap water with the help of a boiler or heat exchanger The energy required for the domestic wat...

Страница 4: ...transportation rope through the forklift stands on the chassis and carrying the boiler with the help of a crane or hoist care should be taken not to damage the painted thin sheets of the boiler and t...

Страница 5: ...ble solution The door of the boiler room should not be opened directly to the escape staircase or general use staircase and must be opened to a common hall or corridor A threshold of at least 10 cm he...

Страница 6: ...dimensions The boiler room should be sized to provide the minimum dimensions given in the picture below While placing the boiler it is necessary to leave sufficient distance for the fuel to be added...

Страница 7: ...ver be used in chimney construction It should be plastered inside and outside and cylindrical pipe inserted into the rectangular chimney It should be ensured that fresh air always enters the area wher...

Страница 8: ...llation water flow rate and the boiler capacity and the 20 C difference between the boiler inlet and outlet water temperatures are not exceeded To minimize the completion of water lost in the installa...

Страница 9: ...te hot dip or c Solid copper rod should be made with electrodes Copper rod electrodes must be at least 1 5 m in diameter of 16 mm or at least 1 25 m in diameter of 20 mm and the earthing resistance of...

Страница 10: ...P a g e 9 KY DUO Boiler User Manual Control panel electrical connection diagram...

Страница 11: ...e flue to the atmosphere The material the way of construction and the connection of the chimneys are important in terms of high combustion efficiency low heating cost and protection of the environment...

Страница 12: ...el may be preferred In order to prevent condensation thermal insulation should be applied to the space between the inner and outer surfaces of the chimney At the lowest level of the chimney there must...

Страница 13: ...rs to circulate the water and circulate the smoke As the smoke passes between them it releases its energy and heats the water inside 3 Water grid They are the pipes for burning Water passes through th...

Страница 14: ...safety due to heating in the boiler 14 Safety return line It is the line where the water sent to the expansion tank is taken back to ensure safety from the boiler 15 Chimney hood It is the boiler sec...

Страница 15: ...31 33 33 35 35 40 Temperature Control Range o C 40 90 Return Temperature Recommended o C 40 Maximum Operating Pressure bar 3 Test Pressure bar 5 Dimensions Boiler Width A mm 1090 1185 1272 Depth B mm...

Страница 16: ...er to prevent the pump shaft from pressing the housing or the outer cover during operation Expansion tank In hot water heating systems when the water is heated from 10 C to 90 C its volume increases b...

Страница 17: ...boilers must be connected to an installation with an open expansion tank in accordance with the installation scheme shown below The circulation pump can be connected on the flow or return line In case...

Страница 18: ...essary measures are taken after the first filling there is no damage caused by the oxygen in the water Oxidation is mostly caused by oxygen which is involved in the heating water during operation The...

Страница 19: ...nstallation Considerations for heating connected to old installations A long term heating system produces a protective layer black magnetite on metal surfaces in contact with water When a new boiler i...

Страница 20: ...on Used to open and close the control panel button Used to input new value to the device Fan Adjustment Temperature Adjustment Fuel Feeding Fuel Standing ENTER Used to store set values and to access s...

Страница 21: ...e of the boiler is switched on and off with this button Fan On Off The fan of the boiler is switched on and off with this button Manual Fuel Feed It is used to load manual manual fuel into the boiler...

Страница 22: ...s and HEATING is not seen because the buttons are not pressed and the boiler does not work Open the boiler lower cover and hold the finger on the Manual Fuel Feed button on the control panel to allow...

Страница 23: ...r right side of the control panel will illuminate and HEAT will appear on the display If the ignition aids in the boiler ignite the fuel press the Reducer On Off button to switch on the gear unit The...

Страница 24: ...oal type can burn in an automatic combustion pot By changing the supplied feeding and waiting settings for this you can catch the most suitable burning setting for the boiler When there is no coal in...

Страница 25: ...cleaned Check that the fan is working properly Unbalanced balanced fan makes periodic noises If there are dust or ash collected between the fins of the fan it is necessary to clean it by blowing it wi...

Страница 26: ...l reservoir hopper Check that there are no holes or cracks in the chimney If you still can t consult your leg Have your chimney sealed Excessive fuel consumption Poor use of fuel may be High chimney t...

Страница 27: ...astic cover on the back of the control panel Activate the limit thermostat by pressing the red pin Turn the control panel off and on Panel over fuel warning is on Fuel in hopper The probe may be displ...