Loop Impedance Z
L
:
Measurement Range:
0,05 ... 19,99
Ω
, 20,0 ... 199,9
Ω
, 200 ... 1999
Ω
Resolution:
0,01
Ω
, 0,1
Ω
, 1
Ω
Tolerance:
±(6% rdg. +5 Digit)
Test current:
< 8A
Load time:
< 80 ms
Mains nominal voltage:
230V, 50...60Hz, cos
ϕ
0,95
Measurement time:
ca. 3s
Max. nominal voltage fluctation during the measurement: 1%
Protective conductor must not be live.
Automatic measurement range selection
Prospective Short-Circuit Current :
Measurement Range:
0,10...9,99A, 10,0...99,9A, 100...999A,
1,00...9,99kA, 10,0...23,0kA
Resolution:
0,01A, 0,1A, 1A, 0,01kA, 0,1kA
Short-circuit current is calculated
Low
Ω
Measurement:
Measurement Range:
0,05 ... 19,99
Ω
Resolution:
0,01
Ω
Tolerance:
±(3% rdg. +5 Digit)
output voltage (with no load) Uq: 5 ... 9V dc
Test Current:
200mA (at resistance < 2
Ω
+Rcomp)
Measurement Time:
1s
Number of Measurements:
1600 (1
Ω
, 1 Measurement - 25s break)
Compensated test lead resistance: max. 1,99
Ω
RCD-Test:
Nominal Voltage:
230V, 50...60Hz
Measurement time:
1s (Pre-Test, Mains-Test)
ca. 31s (Mains-Test time delayed RCD)
max. 18s
Protective conductor must not be live
Measurement of Contact Voltage UB:
Measurement current:
1/3 nominal fault current I
∆
N
Measurement duration:
200ms, when exeeding limits immediate measurement
Measurement Range:
1...63 V
Resolution:
1 V
Tolerance:
-0%...+10%, +5 Digit
Threshold values:
UL selection between 25V / 50V
Contact voltage is measured at 1/3 I
∆
N and may be extrapolated to nominal current I
∆
N or double nominal
current 2 I
∆
N for time delayed residual current circuit breakers.
English
51
Technical Data