Sageon II 200A (N+1) Power Distribution System
Introduction
PM990-5202-200, Rev. 6
1-11
Resolution ............................................... 5mV per cell (2V, 4V, and 6V ranges)
10mV per cell (12V range)
Sampling interval .................................... 1-60 minutes
Sageon Battery Monitor boards .............. 4 maximum / system
Interconnection ....................................... 16-conductor ribbon cable; 30 feet (10m) maximum length
E. Site Monitor
Analog inputs .......................................... 8
Signal range ............................................ 0-5V
Input protection ....................................... Over-voltage and reverse polarity
Signal scaling and alarm levels ............... Scale factor and low and high alarm thresholds are user
programmable at operator panel
Digital inputs ........................................... 12
Signal source ........................................... Voltage free contacts
Logic of digital input .............................. User defined from operator panel
Control outputs........................................ 4
Output signal source ............................... Voltage free form C relay contact; 1A @ 30 Vdc
1.3 PRODUCT SUPPORT
Product support can be obtained using the following addresses and telephone numbers.
Corporate office:
UNIPOWER, LLC
210 N University Dr
Coral Springs, FL 33071
United States
Manufacturing facility:
UNIPOWER, LLC
65 Industrial Park Rd
Dunlap, TN 37327
United States
Manufacturing facility:
UNIPOWER Slovakia SRO
ZLATOVSKA 1279
Business Center 22
91105 Trencin, Slovakia
Phone: +1-954-346-2442
Toll Free: 1-800-440-3504
Web site – www.unipowerco.com
When contacting UNIPOWER, please be prepared to provide:
1.
The product model number, spec number, S build number, and serial number - see the equipment
nameplate on the front panel
2.
Your company’s name and address
3.
Your name and title
4.
The reason for the contact
5.
If there is a problem with product operation:
•
Is the problem intermittent or continuous?
•
What revision is the firmware?
•
What actions were being performed prior to the appearance of the problem?
•
What actions have been taken since the problem occurred?
GENERAL WARNING
1.
This equipment has been designed to be used only in restricted access areas.
2.
This equipment must only be serviced by authorized and qualified service personnel.
3.
Operators should not attempt to repair faulty units. There are no operator serviceable parts inside. All
fuses are only replaced as part of a repair procedure in a repair facility by authorized personnel and not
as a maintenance procedure on site.