Introduction
Sageon II 200A (N+1) Power Distribution System
PM990-5202-200, Rev. 6
1-6
Sageon 200A operation can be monitored at the operator panel on the front of the power system, with a
PC connected to the operator panel, or at a PC connected to the power system over an ethernet network.
Sageon 200A configuration can be performed from the operator panel or at a PC.
Printed circuit boards, in the distribution area contain terminals for user connections to alarm relays,
battery temperature compensation sensors, communications, and other internal and external functions. In
addition, most signals destined for the SCU are routed first to the BDM board or backplane board.
The operator panel provides user access to the configuration and monitoring capabilities of the SCU. For
security, a parameter lock feature is included and PC access can require a password. A PC that is to be
connecting to the Sageon 200A must have the optional Sageview software installed and operating.
1.2 SPECIFICATIONS
This section contains physical, environmental, and electrical specifications for the Sageon 200A and its
major assemblies.
1.2.1 19” Sageon 200A Physical Specifications (1 Tier)
Dimension
200A Sageon II
Power System
200A Sageon II
Power System with AC
Breaker option
Width
19.0" (48.3 cm)
19.0" (48.3 cm)
Depth
9.0" (22.9 cm)
9.0" (22.9 cm)
Height
15.75”(40.0 cm)
19.25”(48.9 cm)
Weight
65 lbs (approx.)
75 lbs (approx.)
IMPORTANT:
The Sageon 200A is shipped without rectifiers. Weight of rectifiers is
additional.
1.2.2 23” Sageon 200A Physical Specifications (2 Tier)
Dimension
200A Sageon II
Power System
200A Sageon II
Power System with AC
Breaker option
Width
23.0" (58.4 cm)
23.0" (58.4 cm)
Depth
9.0" (22.9 cm)
9.0" (22.9 cm)
Height
22.75”(57.8 cm)
26.25”(66.7 cm)
Weight
75 lbs (approx.)
85 lbs (approx.)
IMPORTANT:
The Sageon 200A is shipped without rectifiers. Weight of rectifiers is