Sageview
Sageon II 200A (N+1) Power Distribution System
PM990-5202-200, Rev. 6
5-16
Alarm Name
Comments
LED
HVDC not OK
DC/DC converter (boost) voltage in rectifier not OK
A+R
AC Volt Fault – detected by
rectifiers
All rectifiers are reporting AC fault. (Available only on some rectifier models.)
A+R
AC Volt Fault – detected by
Controller
None of the rectifiers are responding (AC fail assumed), or if AC monitor is used, AC voltage is out of
limits set
(When no AC monitoring module is used, this comes together with “RECTIFIER Comms Fault”)
A
AC Freq Fault
AC frequency lower or higher than preset value
A
Battery Switch
One or more battery switches open
A
Cct Breaker
Fuse or CB in load distribution open
A
LVDS Open
Low Voltage Disconnect switch open
A
Sys Volts High
System output volts too high
A
Sys Volts Low
System output volts too low
A
System V Clamp
CSU can not reach desired system voltage. This can be due to possible excessive voltage drop along bus
bars or “System V Drop” parameter has value too low.
A
Cell V High
One or more cells being monitored by BCM is too high in voltage
A
Cell V Low
One or more cells being monitored by BCM is too low in voltage
A
Cell %dev High
One or more cells being monitored by BCM is too high % deviation from the mean battery
cell voltage
A
Cell %dev Low
One or more cells being monitored by BCM is too low % deviation from the mean battery cell
voltage
A
Range Rectifier
Rectifier parameter range error. Controller could not overwrite values
A
Site Monitor
Alarm present from the site monitor module. See site monitor menu for details of alarm
channel.
A
Battery Disch
Batteries are discharging
A
Disch Tst Fail
Battery discharge test failed to reach a programmed end point
A
Bat Disch Low
Alarm flags only if the system voltage falls below discharge alarm level while the battery is
discharging
A
Rectifier Comms Fail
One or more of rectifiers are not responding
A
Amb Temp High
Ambient temperature higher than preset limit
A
Batt Temp High
Battery temperature higher than preset limit
A
Batt Temp Sens
Battery temperature sensor not connected or failure
A
Batt I-Limit
Battery charging current is being limited to preset value
A
Bat Sym Alarm
Battery discharge currents from battery strings not sharing load equally
A
Earth Leak Alarm
Earth leakage current greater than the limit set
A
Equalize
System is in equalize mode
A *
R = red LED on
A = amber LED flashing
* not flashing
5.12.4 User programmable relay functions
Units are shipped with factory default relay assignments (see below). The relay logic of the default
settings is contact closure on an active alarm. Relay functions can be re-assigned only from a PC running
monitoring program Sageview (either through the front panel USB or remote communications port).
Refer to Sageview Help for instructions.
Relay Default Assignments
1
2
3
4
5
Not Assigned
Not Assigned
HV Shutdown
General Alarm
Rectifier
Shutdown
Customer Relay Assignments
(User to complete)