Configuration and Operation
Sageon II 200A (N+1) Power Distribution System
PM990-5202-200, Rev. 6
4-12
Delta positive voltage threshold: Set the percentage of nominal
cell voltage by which any individual cell voltage can exceed the
nominal. Above this value, an alarm will be generated.
Delta negative voltage threshold: Set the percentage of nominal
cell voltage by which any individual cell voltage can be less than
the nominal. Below this value, an alarm will be generated.
4.5.2 Site Monitor
When the site monitor is included in the software, the window at
right will appear next.
Site monitor On/Off toggle: Press ENTER to display the current
On/Off status (flashing). Press “up arrow” or “down arrow” to
set the desired state, then press ENTER to store.
Contact the factory for additional details concerning this feature.
4.6 RECT (RECTIFIER) MENU SCREENS
Enter this series of menus by pressing the REC (SMR) button. Press “up arrow” or “down arrow” to
select the rectifier number (i.e. rectifier position address) and press ENTER. Press “up arrow” to scroll
through the screens in the order shown. Repeat for each rectifier. The following map summarizes the
available menu screens.
RECT Button
Select rectifier number* (1-24); read
number, current, and temperature
Press ENTER for firmware version
Float voltage
Equalization voltage
Programmable
Voltage, high/low alarm
Voltage, high voltage shutdown
Current limit
Fault, reset SMR
*
The rectifier number is the “rectifier position address” of the
target rectifier (e.g. SMR
“4”
).
SMR No response: A “No Response” message appears when the
target rectifier is not installed, not connected, not switched On,
or is faulty.
SMR initial display: When a rectifier is online and operating
normally, its output current and heatsink temperature are shown.
SMR version and temperature: Press ENTER to display
rectifier’s software version.
Cell +dVc Al
10%
Cell -dVc Al
10%
Site Monitor
Press ENTER
Site Monitor
On
SMR1
No Response
SMR1
32A 29°C
SMR1
G1045a