MANUALE USER SUPPORT
MULTI-THERMOSTAT
MCX06C
MCX06C is a multi-thermostat with four 100k NTC inputs. It can control up to 4 temperatures showing them
(not more than 2 at the same time) on a couple of displays.
It is used to check and adjust oil heater temperatures. it works as follows:
as soon as the burner control gives the GO to the digital 1 input (terminals DI1-COM), the adjustment program runs
(the relevant LED is ON). Reading the outlet temperature through the probe
Pb3
(terminals AI3-COM), a PID
signal is produced. This signal becomes the set-point for the electric resistors. The electric resistors temperature is
read through the probe
Pb1
(terminals AI1-COM) so that a second PID signal is produced. This second PID drives
a couple of SCR by means of 0-10 V impulses in order to control the electric resistors temperature.
When the burner is in stand-by, resistor set-point is kept at the temperature set in parameter "
p30
" (see parameter
group
REG
).
Probe
Pb4
(terminals AI4-COM) controls the inner heater temperature. As soon the relevant set-point is got, it
drives the output number 4 (terminals C4-NO4) linked to the relais KTCN. This allows the oil pump to start and also
the burner control proceeds with its cycle.
When set-point
trS
is got to, output number 5 is ON (terminals C5-NO5) linked to the relais KTRS. It switches the
resistors off and activates an alarm on the device.
Probe
Pb2
(terminals AI2-COM), when fitted, drives output number 2 (terminals C2-NO2) linked to the relais KTCI.
This allows the burner control to proceed with ignition.
See below the set-point recommended figures.
User interface:
Device:
Note :
In normal operation, the display A shows the oil tank resistor temperature (probe Pb1).
In normal operation, the display B shows the oil output temperature (probe Pb3).
Alarm
Display A
Display B
Trains
output
Adjustment
program
running
ESC
button
/
UP
button/
one step
back on the
menu
Escape from the
chosen parameter
/back to the previous
menu
ENTER
button/
Confirmation/ahead
to the next
menu/enter the
parameter to modify
DOWN
button/
one step forward
on the menu
Not used
Warning
COD. M12924CA Rel. 0.5 03/2016
Содержание TN90
Страница 2: ......
Страница 20: ...CIB UNIGAS M039259CA 20 HYDRAULIC DIAGRAMS Fig 8 Hydraulic diagram 3ID0023 Single burner configuration...
Страница 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Страница 34: ...CIB UNIGAS M039259CA 34...
Страница 54: ......
Страница 63: ......
Страница 64: ......
Страница 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 82: ...M12927CA MOUNTING 2...
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......