M12927CA
C
59 SELF
Self tuning enabling
no = The instrument does not perform the self-
tuning
YES = The instrument is performing the self-
tuning
No
A 62 Pb
Proportional band
1... 9999 (E.U.)
See
page 7
A
63 ti
Integral time
0 (oFF) ... 9999 (s)
See
page 7
A
64 td
Derivative time
0 (oFF) ... 9999 (s)
See
page 7
C 65 Fuoc Fuzzy
overshoot control
0.00... 2.00
1
C
69 rS
Manual reset (Integral pre-load)
-100.0... +100.0 (%)
0.0
A
70 Str.t
Servomotor stroke time
5...1000 seconds
See
page 7
A
71 db.S
Servomotor dead band
0...100%
5
C
72 od
Delay at power up
0.00 (oFF) ... 99.59 (hh.mm)
oFF
SP Group - Set point parameters
Liv N° Param
Description
Values
Default
C
76 nSP Number of used set points
1... 4
2
A
77 SPLL Minimum set point value
-1999 ... SPHL
See
page 7
A
78 SPHL Maximum set point value
SPLL ... 9999
See
page 7
O
79 SP
Set point 1
SPLL ... SPLH
See
page 7
C
80 SP 2 Set point 2
SPLL ... SPLH
60
83
A.SP
Selection of the active set point
"SP" ... " nSP"
SP
C
84 SP.rt
Remote set point type
RSP = The value coming from serial link is used
as remote set point
trin = The value will be added to the local set
point selected by
A.SP and the sum becomes the operative set
point
PErc = The value will be scaled on the input
range and this value will be used as remote SP
trin
C
85 SPLr Local/remote set point selection
Loc = Local
rEn = Remote
Loc
C
86 SP.u Rate of rise for POSITIVE set point
change (ramp UP)
0.01... 99.99 (inF) Eng. units per minute
inF
C
87 SP.d Rate of rise for NEGATIVE set point
change (ramp DOWN)
0.01... 99.99 (inF) Eng. units per minute
inF
PAn Group - Operator HMI
Liv N° Param
Description
Values
Default
C
118 PAS2 Level 2 password (limited access level)
oFF (Level 2 not protected by password)
1... 200
20
C
119 PAS3 Level 3 password (complete
configuration level)
3... 300
30
C
120 PAS4 Password livello (livello configurazione a
codice)
201... 400
300
C
121 uSrb button function during RUN TIME
nonE = No function
tunE = Auto-tune/self-tune enabling. A single
press (longer than 1 second)
starts the auto-tune
oPLo = Manual mode. The first pressure puts the
instrument in manual mode
(OPLO) while a second one puts the instrument
in Auto mode
tunE
12
Содержание TN90
Страница 2: ......
Страница 20: ...CIB UNIGAS M039259CA 20 HYDRAULIC DIAGRAMS Fig 8 Hydraulic diagram 3ID0023 Single burner configuration...
Страница 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Страница 34: ...CIB UNIGAS M039259CA 34...
Страница 54: ......
Страница 63: ......
Страница 64: ......
Страница 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 82: ...M12927CA MOUNTING 2...
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......