• InP
typ.
InP
Input settings
dp.s
lo.s
ofs.
Digital filter on input
(if = 0 excludes averaging filter on
sample value)
(*) not available for TC, RTD,
PTC and NTC scales
Digital filter on input
display
Decimal point position for
input scale
Minimum limit of main
input scale
Maximum limit of main
input scale
Offset correction
of main input
0.0 ... 20.0 sec
0 ... 9.9
scale points
dP_S Format
0
xxxx
1
xxx.x
2
xx.xx (*)
3
x.xxx (*)
min...max input range
selected in tyP
min...max input range
selected in tyP
-999 ... 999
scale points
flt
sp.r
Def. remote setpoint
fld
xi.s
0 default (remote setpoint present)
Max. non-linearity error for
thermocouples (TC),
resistors (PT100) and
thermistors (PTC, NTC).
The error is calculated as
deviation from theoretical
value and is expressed as
percentage of full scale
(in °C).
S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other
range; error < 0.5% f.s.
T
error < 0.2% f.s. (t > -150°C)
B
range 44...1800°C; error < 0.5% f.s. (t > 300°C) / range
44,0...999,9; error < 1% f.s. (t > 300°C)
U
range -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other
range; error < 0.2% f.s. (t > -150°C)
G
error < 0.2% f.s. (t > 300°C)
D
error < 0.2% f.s. (t > 200°C)
C
range 0...2300; error < 0.2% f.s. / for other range;
error < 0.5% f.s.
NTC error < 0.5% f.s.
Tc: J, K, E, N, L error < 0,2% f.s.
JPT100 and PTC error < 0,2% f.s.
PT100 scale -200...850°C
Precision better than 0,2% f.s. at 25°C
In range 0...50°C:
• Precision better than 0,2% f.s. in range -200...400°C
• Precision better than 0,4% f.s. in range +400...850°C
(where f.s. refers to range -200... +850°C)
Type
Probe type
without decimal point
with decimal point
Sensore:
TC
0
TC J °C
0/1000
0.0/999.9
1
TC J °F
32/1832
32.0/999.9
2
TC K °C
0/1300
0.0/999.9
3
TC K °F
32/2372
32.0/999.9
4
TC R °C
0/1750
0.0/999.9
5
TC R °F
32/3182
32.0/999.9
6
TC S °C
0/1750
0.0/999.9
7
TC S ° F
32/3182
32.0/999.9
8
TC T °C
-200/400
-199.9/400.0
9
TC T °F
-328/752
-199.9/752.0
28
TC
CUSTOM
CUSTOM
29
TC
CUSTOM
CUSTOM
30
PT100 °C
-200/850
-199.9/850.0
31
PT100 °F
-328/156 2
-199.9/999.9
32
JPT100 °C
-200/600
-199.9/600.0
33
JPT100 °F
-328/1112
-199.9/999.9
34
PTC °C
-55/120
-55.0/120.0
35
PTC °F
-67/248
-67.0/248.0
36
NTC °C
-10/70
-10.0/70.0
37
NTC °F
14/158
14.0/158.0
38
0...60 mV
-1999/9999
-199.9/999.9
39
0...60 mV
Custom scale
Custom scale
40
12...60 mV
-1999/9999
-199.9/999.9
41
12...60 mV
Custom scale
Custom scale
42
0...20 mA
-1999/9999
-199.9/999.9
43
0...20 mA
Custom scale
Custom scale
44
4...20 mA
-1999/9999
-199.9/999.9
45
4...20 mA
Custom scale
Custom scale
46
0...10 V
-1999/9999
-199.9/999.9
47
0...10 V
Custom scale
Custom scale
48
2...10 V
-1999/9999
-199.9/999.9
49
2...10 V
Custom scale
Custom scale
50
0...5 V
-1999/9999
-199.9/999.9
51
0...5 V
Custom scale
Custom scale
52
1...5 V
-1999/9999
-199.9/999.9
53
1...5 V
Custom scale
Custom scale
54
0...1 V
-1999/9999
-199.9/999.9
55
0...1 V
Custom scale
Custom scale
56
200mv..1V
-1999/9999
-199.9/999.9
57
200mv..1V
Custom scale
Custom scale
58 Cust10 V-20mA
-1999/9999
-199.9/999.9
59 Cust10 V-20mA
Custom scale
Custom scale
60
Cust 60mV
-1999/9999
-199.9/999.9
61
Cust 60mV
Custom scale
Custom scale
62
PT100-JPT
CUSTOM
CUSTOM
63
PTC
CUSTOM
CUSTOM
64
NTC
CUSTOM
CUSTOM
Probe type, signal, enable custom linearization,
and main input scale
For custom linearization:
- LO signal is generated with variable below Lo.S or at minimum calibration
value
- HI signal is generated with variable above Lo.S or at maximum calibration
value
+2 Times of pre-heating and gradients of set digit/sec
0
30
0.1
0.5
1
0.0
850.0
0
lo.l
Lower limit for setting SP
and absolute alarms
Lo.S ... Hi.S
Upper limit for setting SP
and absolute alarms
Lo.S ... Hi.S
xi.l
30.0
130.0
5
80379_MHW_600V-T73_06-2012_ENG
Содержание TN90
Страница 2: ......
Страница 20: ...CIB UNIGAS M039259CA 20 HYDRAULIC DIAGRAMS Fig 8 Hydraulic diagram 3ID0023 Single burner configuration...
Страница 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Страница 34: ...CIB UNIGAS M039259CA 34...
Страница 54: ......
Страница 63: ......
Страница 64: ......
Страница 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 82: ...M12927CA MOUNTING 2...
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......