6
ConF > Cntr
Parameter Value
Description
CtYP
controller type
1
2
1 = 3-position controller (open-stop-close only RWF50.2)
2 = continuative action controller (only RWF50.3)
CACt
control action
1
0
1 = heating controller
0 = cooling controller
SPL
least value of the
set-point range
-1999..
0
..+9999
set-point limitation prevents entry of values outside the defined
range
SPH
maximum value of the
set-point range
-1999..
100
..+9999
set-point limitation prevents entry of values outside the defined
range
oLLo
set-point limitation
start, operation limit
low
-1999
.... +9999
lower working range limit
oLHi
set-point limitation
end, operation limit
high -1999....
+9999
upper working range limit
(
bold
= factory settings)
ConF > rAFC
Activation boiler shock termic protetion:
RWF50.. can activate the thermal shock protection only on sites where the set-point is lower than 250°C and according
to
rAL
parameter.
Parameter Value
Description
FnCT
function
0
1
2
Choose type of range degrees/time
0 = deactivated
1 = Kelvin degrees/minute
2 = Kelvin degrees/hour
rASL
ramp rate
0,0 …
999,9
Slope of thermal shock protection (only with functions 1 and 2)
toLP
tolerance band ramp
0
…9999
width of tolerance band (in K) about the set-point
0 = tolerance band inactive
rAL
ramp limit
0
…250
Ramp limit. When this value is lower than the temperature set-
point, the RWF controls the output increasing the temp set
point step by step according to rASL. If this is over the temp set
point, the control is performed in cooling.
(
bold
= factory settings)
Содержание TN90
Страница 2: ......
Страница 20: ...CIB UNIGAS M039259CA 20 HYDRAULIC DIAGRAMS Fig 8 Hydraulic diagram 3ID0023 Single burner configuration...
Страница 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Страница 34: ...CIB UNIGAS M039259CA 34...
Страница 54: ......
Страница 63: ......
Страница 64: ......
Страница 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 82: ...M12927CA MOUNTING 2...
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......