Nozzle and electrodes correct position
.Place the nozzle according to the combustion head; unscrew
VB
and move the combustion head. Check the ignition electrodes at the
end of the procedure. Quotes are referred in mm.
Fig. 17
Checking the detection current
To check the flame itensity signal, follow the diagram shown on the next picture. If the measured value is lower than the suggested one,
check the photoresistor/photocell position, the electrical contacts. Replace the photoresistor/photocell if necessary.
Cleaning and replacing the detection photoresistor
When cleaning the photoresistive detector, always use a clean cloth. If necessary, remove it from its slot to replace it.
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel valve of the supply line
Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
Fig. 18
VB
Control box
Minimum detection signal
LAL2..
8 µA (QRB)
LAL2..
6,5 µA (RAR)
34 35
SCALE µA DC
MA TERMINAL BLOCK
Содержание TN90
Страница 2: ......
Страница 20: ...CIB UNIGAS M039259CA 20 HYDRAULIC DIAGRAMS Fig 8 Hydraulic diagram 3ID0023 Single burner configuration...
Страница 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Страница 34: ...CIB UNIGAS M039259CA 34...
Страница 54: ......
Страница 63: ......
Страница 64: ......
Страница 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 82: ...M12927CA MOUNTING 2...
Страница 106: ......
Страница 107: ......
Страница 108: ......
Страница 109: ......
Страница 110: ......
Страница 111: ......
Страница 112: ......