background image

  SK00-4167-DI-002-07 

16 

 

3.

 

Gas-ballast Valve 

This product is installed with the gas ballast function as standard. PVD-180-H, -360-H has no gas 

ballast valve. 

Breathed condensed gas shall be liquefied through the compress process of the Pump, mixed with 

the Pump oil and then cycled mixed together inside the Pump unit. This status brings you the same 
situation that you used the high steam pressure oil that raises the ultimate pressure. It also shortens 
the life cycle of the Shaft seal since the oil lubrication shall deteriorate. 

If introduced the air or dry nitrogen through the gas ballast valve just before the Pump compression 

process, the condensed gas is not liquefied but exhausted with the air through the Exhaust valve. 

To  use  the  gas  ballast,  breathe  in  the  air  through  the  gas  ballast  valve  before  sucking  in  the 

condensed gas and operate the Pump around twenty minutes; this is because the “gas ballast effect” 

becomes larger as the Pump temperature is higher. Wait until the Pump temperature raises enough to 
open the Vacuum Valve so as to operate the Pump. The “gas ballast effect” under low temperature 
shall be lower than the specified process performance. 

Note further that keeping the gas ballast valve open when not breathing in the condensed gas shall 

cause the Pump oil splashing and power loss and further rise the ultimate pressure. You have to note 
also that the condensed gas might remain in the Pump oil after you have exhausted a lot of condensed 
gas  or  exhausted  the  condensed  gas  (air  or  gas  that  contains  less  water  or  other  steam  that 
contaminates the oil) without opening the gas ballast valve since the process capacity of the condensed 
gas by the gas ballast valve is limited. 

In such a case, close the Main valve, breathe in the air through the gas ballast valve and idle operate 

the Pump. Then the oil temperature shall rise up and be cleaned by means of the Gas ballast effect. 
Keep on idle operating the Pump without opening the gas ballast valve as far as the specified ultimate 
pressure is attained. You need to replace the Pump oil if it was not cleaned after operated long time. 
Note: The Vacuum pump gets high temperature during operation. As the gas ballast valve also gets 

high temperature, be sure to wear protective gear such as a pair of gloves. 

Note: Ensure to close the gas ballast valve to start operating the Pump. The oil might jet out of the gas 

ballast valve during the operation around high pressure range. 

Note:

 

The guaranteed pressure resistance of this pump is 0.03 MPa (0.3 kg / cm2) (gauge pressure).

 

Operate the supply pressure of the gas ballast gas to be introduced within the following range. 
Supply pressure: Atmospheric pressure to 0.03 MPa (0.3 kg / cm2 (gauge pressure)) or less.

 

 

4.

 

Vacuum Pump Oil ULVOIL R-42 for Winter Use 

In winter, if the pump could not be started easily, check the following points carefully. [Belt-tension, 

Motor fuse, smoothness of rotation of the pump, etc.].    In spite of normal behavior for the check points, 
if the pump could not be started easily, please replace oil to ULVOIL R-42. 
Note: It is better to use the ULVOIL R-42 having less viscosity that enables you to start rotating the 

Pump around 4

. Replace it with the ULVOIL R-72 if the temperature gets 10

  or more. Be 

cautious as using the ULVOIL R-42 in warm season would cause such troubles as sealing error, 
oil leak or more serious trouble, due to its lower viscosity.   

Note:  ULVOIL  R-42  is  unfitted  for  high  load  operation.  When  performing  the  high  load  operation,  use 

ULVOIL R-72, and either warm the Pump oil or perform the Pump jog at several times, and start it 
up.

 

 

 

Содержание PVD-180

Страница 1: ...MANUAL OIL SEALED ROTARY VACUUM PUMP PVD 180 PVD 180B PVD 360 PVD 360B Before using this product be sure to read this operation manual Keep this manual with care to use at any time ULVAC Inc Component...

Страница 2: ......

Страница 3: ...16 5 Oil mist trap Option 17 Pump Performance 17 1 Ultimate Pressure 17 2 Pumping Speed 18 3 Power Requirements 19 Maintenance and Check 20 1 Maintenance 20 2 Regular Check 20 2 1 Check and Replace V...

Страница 4: ...g 12 Connection with Vacuum System for PVD 180 PVD 360 13 Fig 13 Connection 1 with Vacuum System for PVD 180B PVD 360B 14 Fig 14 Connection 2 with Vacuum System for PVD 180B PVD 360B 14 Fig 15 Connect...

Страница 5: ...uches the unit it may get burned 4 This product is not made as the withstand pressure structure Ensured pressure value of the Pump shall be 0 03MPaG 0 3kg cm2G Gauge pressure Do not run the Pump on bl...

Страница 6: ...el is put Do not open a panel or a safety cover during operation You should turn off the power line of the moving part If the power of this Pump doesn t supply the moving part may have a possible to m...

Страница 7: ...t function according to your application It is applicable to breathe in the condensed gas such as the steam and solution vapor Note Spec H don t have the gas ballast function 2 Oil anti sack backflow...

Страница 8: ...Spec H External leak test It is inspected before shipment if helium leak rate from outside to the Pump is less than 10 6 Pa m3 sec helium leak test by hood test method Leak rate will increase due to a...

Страница 9: ...ional TMX 1 Options Oil mist trap RF explosion resistant motor Special application Spec K H and Z 1 Measured with a Pirani gauge Approx 6 7X10 2 Pa when measured with a McLeod vacuum gauge 2 The pump...

Страница 10: ...SK00 4167 DI 002 07 6 3 Dimensional drawing Fig 2 Dimensional drawing PVD 180 Fig 3 Dimensional drawing PVD 360...

Страница 11: ...SK00 4167 DI 002 07 7 Fig 4 Dimensional drawing PVD 180B Fig 5 Dimensional drawing PVD 360B...

Страница 12: ...SK00 4167 DI 002 07 8 Fig 6 Dimensional drawing PVD 180 H RF 1 RF 7 Fig 7 Dimensional drawing PVD 360 H RF 3 RF 8...

Страница 13: ...SK00 4167 DI 002 07 9 Fig 8 Dimensional drawing PVD 180 H RF 2 Fig 9 Dimensional drawing PVD 360 H RF 5...

Страница 14: ...e set the pump horizontally on a rigid floor The PVD pump is almost free from vibration during operation and has no need of anchor bolts in mounting The base of the pump should be however installed re...

Страница 15: ...an electromagnetic switch with thermal relay for remote starting Use the safety circuit capacity shown in Table 4 Attention Be sure to use the motor breaker Since a current 5 to 10 times the rated cur...

Страница 16: ...andard motors Should you use other motor confirm the specific by the motor nameplate 5 Fit the V belt 6 Connect the solenoid valve B TYPE Applied only for Type PVD 180B or 360B The electrical supply t...

Страница 17: ...n the suction port of the pump to prevent larger solids from entering the pump Do not take the wire net off The net should be washed and cleaned periodically according to your specific maintenance sch...

Страница 18: ...uipment and the vacuum pump is required for PVD 180 H and PVD 360 H as shown in Fig 16 When the pump stops shut the vacuum valve A to keep the equipment in vacuum then open the leak valve B and let ai...

Страница 19: ...contact the closest Service Center 4 When the pump is kept running for several hours the oil temperature in the case will rise to about 70 at a room temperature around 60 65 If the oil temperature ex...

Страница 20: ...lve is limited In such a case close the Main valve breathe in the air through the gas ballast valve and idle operate the Pump Then the oil temperature shall rise up and be cleaned by means of the Gas...

Страница 21: ...he most favorable condition using new specified pump oil by means of a vacuum gauge installed at the suction pipe of the pump the rest of the vacuum system should be functionally disconnected from the...

Страница 22: ...ending on the type and pressure of the sucked gas It shall indicate the maximum exhaust speed in the high pressure range and lower speed little by little lower becomes the pressure PVD 180 H 360 H has...

Страница 23: ...e Pump shall indicate the largest load pressure range while the suction pressure was between 2 7 104 4 104 Pa Operation opening the gas ballast valve would require larger motive energy at all the time...

Страница 24: ...ltimate pressure is rise leading to poor function of the mechanical friction parts of the Pump In the worst case the Pump will seize up and cannot be rotated The vacuum pump oil will be gradually dete...

Страница 25: ...en the life time by overheat The pump is not start or not perform pumping speed Initial wear Early operation the belt tension decreases by the extension and fall in the pulley groove Re tension the be...

Страница 26: ...over 3 Set the Ring for Deflection to 5mm 4 Set the Ring for Load to 0N 5 Push the center of the belt between the motor pulley and the pump pulley down 5mm with tension meter 6 Read the load after pus...

Страница 27: ...is dirty please wash that Further it is anticipated that any welding scale drops off in the pipe particularly at the beginning of the system start Be fully cautious 2 6 Checking Noise and Abnormal Vib...

Страница 28: ...PVD 180 B JIS B 2401 P 22A 1 PVD 360 B JIS B 2401 P 30 1 Solenoid Valve Only PVD 180B 360B CKD AB3X Custom made 1 AL Gasket Only PVD 180B 360B 10 13 t1 5 1 Table 7 PVD 180 H PVD 360 H Main replacemen...

Страница 29: ...the power supply 9 Are the Safety circuit such as a MS Magnetic Switch and MCCB Molded Case Circuit Breaker normal Trips Right the cause of trips Reset 10 Are the Safety circuit such as a MS Magnetic...

Страница 30: ...b Dust is being suctioned c Solvent vapor is being suctioned d Foreign substance enters in Replace with new oil Conduct the overhaul Inside cleaning a Put the trap into the front stage of the Pump b P...

Страница 31: ...on starting or stopping the machine There is no particular problem as it s a phenomenon caused by vanes that temporarily make irregular motions 9 The tension of the belt is loose Replace and Re tensio...

Страница 32: ...n substance entered inside the Pump impaired the Motor rotation Conduct the overhaul Removal of foreign substance inside the Pump 2 There is a leak in the pipe connecting with the Pump Use a Leak dete...

Страница 33: ...ard specifications although this product is used under the service conditions described in this document such as temperature range and power etc 2 Direct export transaction Product which has damage ca...

Страница 34: ...AC for patent infringement 9 ULVAC engineer decided the reason of failure was improper use which does not conform to the use condition of this Product 10 Consumable parts refer to 9 Main Displacement...

Страница 35: ...ty period Table 9 Making format for names and contents of hazardous substances or elements Name of parts Hazardous substances or elements Pb Hg Cd Cr6 PBB PBDE Body indicating that content of the haza...

Страница 36: ...ion Remarks Contaminant Check an applicable box I guarantee that above returned item s is not contaminated with harmful substances Above returned item s is contaminated with the following harmful subs...

Страница 37: ......

Отзывы: