UDEVAC-500
Front panel
1. Equipment power indicator.
Green
system has an AC or DC power failure.
Yellow
system works well AC and DC supplies are normal.
2. Equipment and system status indicators (FAULT)
Yellow
failure of some module or system equipment, please press "
FAULT ACK
" to cancel the warning
buzzer.
(blinking)
new failure in the equipment, to inform the user.
Off
all modules in the system are operating normally.
3. Handheld microphone status indicator
Green
microphone is working, giving a warning.
Yellow
the microphone is faulty.
Off
microphone is normal.
4. Handheld microphone status indicator
In any state, press this button and all LEDs will light. Used to confirm that the LEDs are working properly.
5. Emergency button and indicator.
Red (blinking)
equipment is in emergency mode.
Off
equipment is normal mode.
To make an emergency warning broadcast:
A)
) Activate emergency mode by pressing the red button with cover and immediately the red light will start
flashing. and then press the
EVAC MSG
or
ALERT MSG
buttons, which will activate the warning in all zones of
the system.
B)
The automatic transmission of an emergency will be activated by closing any of the rear inputs remote
controls of the control unit or the expansion unit and the red light will flash.
Emergency mode reset:
A)
Press the
ACK / RESET
button on the front panel to end the emergency mode and to end the emergency
message broadcast.
B)
The automatic way to exit the emergency mode is with a direct short-circuit in the
Emergency Reset Input
on the rear panel of the SLA-500M, and then the playback of the evacuation voice message will stop and the
exit zones will speakers will be disconnected. These events are logged and can be viewed in the SF-500
software's history (LOG).