6. FAULT ACK button
A)
All the modules of the system are supervised and the diagnosis is normal, if we press this button when the
FAULT
light is not flashing, the equipment will not do any action or process.
B)
) If any module in the system has any fault, the
FAULT
indicator light will flash, press the
FAULT ACK
button
and the
FAULT
indicator will stop flashing and the buzzer will stop until another fault is detected then the
FAULT
indicator starts to flash again and the buzzer to sound.
7. EVAC & ALERT Message buttons and indicators.
Green
voice message or alert is playing
EVAC MSG / ALERT MSG
Yellow
a voice message, alert or the SD card has failed.
Off
voice message or alert is not being played.
If you need to manually play the evacuation voice messages, you need to enter the emergency mode and then
press the
EVAC MSG
or
ALERT MSG
button.
By default in the system the evacuation message has priority over the alert message. You can change the
priority through the SF-500 software. If due to special installation requirements it is not essential, please do not
change it.
8. Programmable function buttons and indicators.
Blink indicator
programmed function is active
Off
programmable functions are disabled
9. Lock
10. Hand microphone
It is mainly used to guide people in an emergency situation:
11. Wiring entry
12. DIP switch for setting the device ID (addressing). Configuration of the "ID" of the equipment by
means of the DIPs.
Raised in position
ON
means that it is activated and lowered means disabled. From the 1st to the 5th switch
are to configure the address / identification of the microphone through a binary system. The 6th switch up
means that the voice prompts mode is normal and down means the voice prompts mode in PTT mode. The 7th
switch up means that this microphone gives announcements in individual zones and down means that the
group of zones for the announcement of this microphone, as a group could be defined with several zones.
The 8th switch is to activate all the LEDs as a test of these indicative LEDs, downwards it activates the test of
the LED indicators, all the LED indicators will light up in red-green-yellow to know their normal operation.
Below is an example configuration of the announcement microphone from number 1 to 4.
2
4
16
8
PTT
Z/G
1
VALORES ASIGNADOS A CADA DIP
Test
2
3
ON
5
4
6
7
8
1
2
4
16
8
PTT
Z/G
1
VALORES ASIGNADOS A CADA DIP
Test
2
3
ON
5
4
6
7
8
1
2
4
16
8
PTT
Z/G
1
VALORES ASIGNADOS A CADA DIP
Test
2
3
ON
5
4
6
7
8
1
2
4
16
8
PTT
Z/G
1
VALORES ASIGNADOS A CADA DIP
Test
2
3
ON
5
4
6
7
8
1
36
14
610.592A
Rev.
1
UDEVAC-500
Values assigned to each DIP switch