8.2.5 Voltage drop for actuator
chain
This paragraph shows examples of drop voltage in
case of actuators connected in chain.
The diagram shows the typical voltage drop of
actuators with stroke of 1000 mm operating
at maximum load and cables supplied by UCS.
The allowed voltage (24 Vdc +/- 15%) must
be checked on the first and last actuator of
the chain. If necessary, adjust the feeder
voltage so that the maximum limit (27.6 V)
for the first actuator of the chain while the
actuators are operating and the minimum
one (20.4) for the last actuator of the chain
are not exceeded.
WARNING
WARNING
In case of different strokes or use conditions, a
check by UCS may be needed.
42016T white cable kit
42017U black cable kit
42016T kit cavo bianco
42017U kit cavo nero
*
**
42018V white double connector cable
42019W black double connector cable
42018V cavo doppio connettore bianco
42019W cavo doppio connettore nero
ΔV
= 2.5V
ΔV
= 5V
LENGTH = 1m
LUNGHEZZA = 1m
LENGTH = 1,5m
LUNGHEZZA = 1,5m
42021Y NANO electric connector kit
42021Y kit connettore elettrico NANO
8.2.5 Cadute di tensione per catena
di attuatori
Questo paragrafo riporta esempi di caduta di ten
-
sione nel caso di una catena di attuatori.
Lo schema mostra la caduta di tensione tipica
per attuatori con corsa di 1000 mm funzionanti
a pieno carico e con cavi forniti da UCS.
L’indicazione di tensione consentita (24 Vdc +/-
15%) deve essere verificata sul primo e sull’ultimo
attuatore della catena. Eventualmente, regolare
la tensione emessa dall’alimentatore in maniera
che non superi il limite superiore (27.6 V) per il
primo attuatore della catena mentre gli attuatori
sono in funzione e non scenda sotto il limite
inferiore (20.4) per l’ultimo attuatore della catena.
ATTENZIONE
ATTENZIONE
In caso di differenti corse o condizioni di utilizzo,può
essere necessaria una verifica da parte di UCS.