TFP480

Page 8 of 12

SELECT NORMALLY OPEN

SELECT NORMALLY OPEN

SELECT NORMALLY OPEN

OR NORMALLY CLOSED

CRIMPED ON CONNECTOR

NYLON

INSULATED

RING

GROUND

SWITCH

COMPRESSOR DISCONNECT

120 V

AC

WIRED

FIELD

BLK

RED

(NEUTRAL)

CRIMPED ON

CONNECTORS

(LINE)

-

+

-

+

POS

NEG

POS

NEG

24 VDC

+

-

BATTERIES

TWIST-ON WIRE

CONNECTORS

CONNECTED

FIELD

RELAY #3

OR NORMALLY CLOSED

RELAY #2

OR NORMALLY CLOSED

AIR

M

COMPRESSOR

TROUBLE RELAY

1/2 W

1/2 W

10k Ω

1/2 W

10k Ω

1/2 W

3.3k Ω

1/2 W

3.3k Ω

3.3k Ω

RAC 1 RAC 2

-

+

-

+

NAC 1 NAC 2

-

+

-

+

12-18 AWG

1A MAX.

NOTIFICATION

CIRCUIT

IDC 2

IDC 1

+

-

+

-

IDC 4

IDC 3

-

+

-

+

1/2 W

3.3k Ω

SPM 2

SPM 1

+

+

-

-

+

-

R

SOLENOID

PRE-CONNECTED

YEL

RED

(TYPICAL)

430687

TWIST-ON WIRE

CONNECTOR

RED

SUPERVISION

COIL

MODULE

YEL

S

BLK

BLK

PRESSURE

LOW AIR

@ 8 PSI

BLK

VALVE

CONTROL

MAIN

VALVE

CONTROL

SYSTEM

PRE-CONNECTED

LISTED

PRE-CONNECTED

1/2 W

BLK

ANNUNCIATORS

10k Ω

FIELD WIRED

1/2 W

3.3k Ω

HIGH AIR

@ 20 PSI

SWITCH

PRESSURE

1/2 W

3.3k Ω

USE

DO NOT

24 V POWER

0.25A MAX.

AUXILIARY

DO NOT

USE

DO NOT

USE

DO NOT

USE

DO NOT

USE

OPTIONAL

FIGURE 4 

MODEL RCP-1 RESIDENTIAL CONTROL PANEL  

ELECTRONIC CONTROL WIRING DIAGRAM 

Содержание RAPID RESPONSE RCP-1

Страница 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Страница 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Страница 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Страница 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Страница 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Страница 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Страница 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Страница 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Страница 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Страница 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Страница 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Страница 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...