background image

TFP480

Page 7 of 12

KEYS

• 

ACCEPT SIGNAL KEY

The system LEDs (ALARM, SUPER-

VISORY, TROUBLE) flash to indi-

cate the presence of an unaccepted 

alarm, supervisory, or trouble condi-

tion somewhere in the system. The 

ACCEPT SIGNAL KEY acknowledg-

es the presence of an alarm, super-

visory, or trouble condition. 
By momentarily pressing the AC-

CEPT SIGNAL KEY, the flashing LED 

turns steady. The ACCEPT SIGNAL 

KEY is used to acknowledge every 

abnormal status present in the sys-

tem. For example, if there are two 

red alarms and three yellow troubles, 

the ACCEPT SIGNAL KEY must be 

pressed five times. 
The Panel’s tone-alert turns off when 

all abnormal conditions are accepted. 

• 

SIGNAL SILENCE KEY

Pressing the SIGNAL SILENCE KEY 

silences the audible notification de-

vices (horns). The Yellow ALARM SI-

LENCED LED lights to indicate that 

an alarm is still active even if the au-

dible alarms have been silenced. 

• 

SYSTEM RESET KEY

Pressing the SYSTEM RESET KEY 

directs the Panel to reset all at-

tached devices and clear all accept-

ed alarms, troubles, and supervisory 

conditions. All alarms must first be 

accepted via the ACCEPT SIGNAL 

KEY and all devices must be reset 

(that is, normal system air pressure 

is re-established). 

Note:

 After pressing the SYSTEM 

RESET KEY, the panel requires ap-

proximately fifteen seconds to clear. 

In Case of 

Supervisory/ 

Trouble 

Condition

Step 1.

 Verify that a fire condition does 

not exist. 

Step 2. 

Close the Main Control Valve 

to prevent inadvertent water flow into 

the system. 

Step 3. 

Acknowledge the superviso-

ry/trouble notification by momentarily 

pressing the ACCEPT SIGNAL KEY. 

Doing so silences the tone-alert.

Step 4. 

Determine and correct cause 

of supervisory/trouble notification, for 

example: 

• 

Loss of primary 120 VAC power 

• 

 Low battery condition 

• 

 High air pressure 

• 

System or main control valve closure 

Step 5. 

Reset the system as soon as 

possible. 

In Case of  

Alarm Condition

Step 1. 

Verify that a fire condition ex-

ists and take appropriate action (that 

is, evacuate the building and call fire 

department). 

Step 2. 

After the fire is extinguished, 

reset the system. 
If a fire condition does not exist and pri-

or to resetting the system, silence the 

alarms as follows: 

• 

First, momentarily press the ACCEPT 

SIGNAL KEY a sufficient number of 

times to stop the tone-alert. 

• 

Second, momentarily press the SIG-

NAL SILENCE KEY. 

System 

Resetting

Step 1. 

Use the ACCEPT SIGNAL KEY 

to accept every abnormal status pres-

ent in the system. 
For example, when two red ALARM 

and three yellow TROUBLE conditions 

are present, the ACCEPT SIGNAL KEY 

must be pressed five times. The Panel’s 

tone-alert turns off when all abnormal 

conditions are accepted. 

Step 2. 

Silence the alarms by pressing 

the SIGNAL SILENCE KEY. 

Step 3. 

Close the Main Control Valve. 

Step 4. 

Place the Air Compressor Dis-

connect Switch to the OFF position. 

Step 5. 

Open the Drain and Flow Test 

Valves. 

Step 6. 

Replace operated sprinklers. 

Step 7. 

After the system drains com-

pletely, close the Drain and Flow Test 

Valves. 

Step 8. 

Place the Air Compressor Dis-

connect Switch to the ON position and 

allow the system to automatically rees-

tablish its normal air pressure of 10 to 

14 psi. 

Step 9. 

Reset the Electronic Control by 

pressing the SYSTEM RESET KEY. 
Wait approximately fifteen seconds for 

the Electronic Control to clear.
A supervisory signal will remain be-

cause the Main Control Valve is still 

closed.
Press the ACCEPT SIGNAL KEY to ac-

cept the supervisory signal and silence 

the tone-alert. 

Step 10. 

Slowly open the Main Control 

Valve. (Opening the Control Valve too 

quickly may result in activation of the 

pressure switch.)
The supervisory signal should clear and 

the system is now set for service. 

NOTICE

After pressing the SYSTEM RESET 

KEY, the panel requires approximately 

fifteen seconds to clear. 

Содержание RAPID RESPONSE RCP-1

Страница 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Страница 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Страница 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Страница 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Страница 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Страница 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Страница 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Страница 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Страница 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Страница 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Страница 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Страница 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...

Отзывы: