![Tyco RAPID RESPONSE RCP-1 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/tyco/rapid-response-rcp-1/rapid-response-rcp-1_manual_1185694006.webp)
TFP480
Page 6 of 12
Operator
Interface
The Model RCP-1 Panel uses LEDs and
KEYs as its primary means of display-
ing status information and controlling
the system. It allows the occupants to
monitor the status of the Model RCP-1
Panel and its circuits.
The LEDs are located along the left
and right sides of the Operator Inter-
face (Figure 3). Three KEYs are located
along the lower edge of the Operator
Interface.
LEDs
•
ALARM LEDs
A flashing red LED adjacent to the
SPRINKLER (IDC1) indicates an
alarm.
•
TROUBLE LEDs
A flashing yellow Trouble LED for one
of the IDCs, NACs, or RACs indi-
cates the presence of a circuit break
or ground within a system point, or
somewhere in the wiring between the
control panel and one of its points.
•
SUPERVISORY LED
A flashing yellow SUPERVISORY LED
indicates a problem with the condi-
tion of the sprinkler system controls
or normal status (for example, closed
valve position for Main Control Valve,
closed valve position for System
Control Valve, or high air condition).
•
SYSTEM TROUBLE LED
When a TROUBLE condition occurs,
the SYSTEM TROUBLE LED flash-
es until accepted. When accepted, it
changes from flashing to steady.
•
AC POWER LED
When lit steady, the Green AC
POWER LED indicates that the Elec-
tronic Control of the Model RCP-1
Panel is receiving AC power that is
within the specified range.
If the LED is not lit and the Panel is
still functioning, the Electronic Con-
trol is using battery power to oper-
ate. The cause for loss of AC Power
should be determined and correct-
ed. The system is in a normal stand-
by condition when only the Green AC
POWER LED is ON.
•
SYSTEM RELEASED LED
The Red SYSTEM RELEASED LED
turns on steady when the RAC circuit
is activated. Activation of the RAC cir-
cuit energizes the Solenoid Valve to
permit water to enter the sprinkler
system piping. RAC1 is utilized, and
RAC2 is spare.
•
EARTH FAULT LED
The Yellow EARTH FAULT LED turns
on steady when there is a wiring fault
from circuit to Earth.
•
Lamp (LED) Test
A lamp (LED) test can be performed
by pressing and holding the AC-
CEPT SIGNAL KEY for a duration
of five seconds. Performing a lamp
test lights all LEDs on the system
and verifies that all system LEDs are
functioning.
Panel
Reference
Description
IDC
Initiating Device Circuit
(Low Air Pressure)
NAC
Notification Appliance Circuit
(Optional Notification Appliance)
RAC
Releasing Appliance Circuit
(Solenoid Valve)
SPM
Special Purpose Monitor
(Main Control Valve Closure,
System Control Valve Closure, or
High System Air Pressure)
KEYS
LEDs
ACCEPT
SIGNAL
SIGNAL
SILENCE
SYSTEM
RESET
TROUBLE
ALARM
TROUBLE
ALARM
TROUBLE
ALARM
ALARM
TROUBLE
ALARM SILENCED
AC POWER
SUPERVISORY (SMP1)
SYSTEM TROUBLE
(IDC4)
SPARE (RAC2) TROUBLE
SYSTEM RELEASED
EARTH FAULT
SPARE
SPARE
SPARE (NAC2) TROUBLE
(NAC1) TROUBLE
(RAC1) TROUBLE
SPRINKLER
SPARE
SPARE
(IDC3)
SPARE
(IDC2)
(IDC1)
SPARE
(SMP2)
(SMP1)
DRY PIPE SYSTEM
TROUBLE
ALARM
TROUBLE
FIGURE 3
OPERATOR INTERFACE CARD (FRONT SIDE)
DRY PIPE SYSTEM MODE