Tyco RAPID RESPONSE RCP-1 Скачать руководство пользователя страница 6

TFP480

Page 6 of 12

Operator  

Interface 

The Model RCP-1 Panel uses LEDs and 

KEYs as its primary means of display-

ing status information and controlling 

the system. It allows the occupants to 

monitor the status of the Model RCP-1 

Panel and its circuits. 
The LEDs are located along the left 

and right sides of the Operator Inter-

face (Figure 3). Three KEYs are located 

along the lower edge of the Operator 

Interface. 

LEDs

• 

ALARM LEDs

A flashing red LED adjacent to the 

SPRINKLER (IDC1) indicates an 

alarm. 

• 

TROUBLE LEDs

A flashing yellow Trouble LED for one 

of the IDCs, NACs, or RACs indi-

cates the presence of a circuit break 

or ground within a system point, or 

somewhere in the wiring between the 

control panel and one of its points. 

• 

SUPERVISORY LED

A flashing yellow SUPERVISORY LED 

indicates a problem with the condi-

tion of the sprinkler system controls 

or normal status (for example, closed 

valve position for Main Control Valve, 

closed valve position for System 

Control Valve, or high air condition). 

• 

SYSTEM TROUBLE LED

When a TROUBLE condition occurs, 

the SYSTEM TROUBLE LED flash-

es until accepted. When accepted, it 

changes from flashing to steady. 

• 

AC POWER LED

When lit steady, the Green AC 

POWER LED indicates that the Elec-

tronic Control of the Model RCP-1 

Panel is receiving AC power that is 

within the specified range. 
If the LED is not lit and the Panel is 

still functioning, the Electronic Con-

trol is using battery power to oper-

ate. The cause for loss of AC Power 

should be determined and correct-

ed. The system is in a normal stand-

by condition when only the Green AC 

POWER LED is ON. 

• 

SYSTEM RELEASED LED

The Red SYSTEM RELEASED LED 

turns on steady when the RAC circuit 

is activated. Activation of the RAC cir-

cuit energizes the Solenoid Valve to 

permit water to enter the sprinkler 

system piping. RAC1 is utilized, and 

RAC2 is spare. 

• 

EARTH FAULT LED

The Yellow EARTH FAULT LED turns 

on steady when there is a wiring fault 

from circuit to Earth. 

• 

Lamp (LED) Test

A lamp (LED) test can be performed 

by pressing and holding the AC-

CEPT SIGNAL KEY for a duration 

of five seconds. Performing a lamp 

test lights all LEDs on the system 

and verifies that all system LEDs are 

functioning. 

Panel 

Reference

Description

IDC

Initiating Device Circuit

(Low Air Pressure)

NAC

Notification Appliance Circuit

(Optional Notification Appliance)

RAC

Releasing Appliance Circuit

(Solenoid Valve)

SPM

Special Purpose Monitor

(Main Control Valve Closure,  

System Control Valve Closure, or  

High System Air Pressure)

KEYS

LEDs

ACCEPT

SIGNAL

SIGNAL

SILENCE

SYSTEM

RESET

TROUBLE

ALARM

TROUBLE

ALARM

TROUBLE

ALARM

ALARM

TROUBLE

ALARM SILENCED

AC POWER

SUPERVISORY (SMP1)

SYSTEM TROUBLE

(IDC4)

SPARE (RAC2) TROUBLE

SYSTEM RELEASED

EARTH FAULT

SPARE

SPARE

SPARE (NAC2) TROUBLE

(NAC1) TROUBLE

(RAC1) TROUBLE

SPRINKLER

SPARE

SPARE

(IDC3)

SPARE

(IDC2)

(IDC1)

SPARE

(SMP2)

(SMP1)

DRY PIPE SYSTEM

TROUBLE

ALARM

TROUBLE

FIGURE 3  

OPERATOR INTERFACE CARD (FRONT SIDE) 

DRY PIPE SYSTEM MODE

Содержание RAPID RESPONSE RCP-1

Страница 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Страница 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Страница 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Страница 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Страница 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Страница 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Страница 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Страница 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Страница 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Страница 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Страница 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Страница 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...

Отзывы: