background image

TFP480

Page 11 of 12

Care and  

Maintenance 

Before closing a fire protection system 

control valve for inspection or mainte-

nance work on the fire protection sys-

tem that it controls, obtain permission 

to shut down the effected fire protec-

tion system from the proper authorities 

and notify all personnel who may be af-

fected by this action. 
The following inspection/test proce-

dures will result in operation of the as-

sociated alarms. Notify the proper au-

thorities and advise those responsible 

for monitoring proprietary and/or cen-

tral station alarms. 
After placing a fire protection system 

in service, notify proper authorities and 

advise those responsible for monitor-

ing proprietary and/or central station 

alarms. 

The following inspection/test procedure 

for the RAPID RESPONSE Model RCP-

1 Residential Control Panel must be 

performed as indicated, in addition to 

any specific requirements of the NFPA. 

Any impairment must be immediately 

corrected. 
The owner responsible for the inspec-

tion, testing, and maintenance of their 

fire protection system and devices in 

compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associa-

tion (e.g., NFPA 25), in addition to the 

requirements of any authority having 

jurisdiction. The installing contractor or 

product manufacturer should be con-

tacted relative to any questions. 
Automatic sprinkler systems are recom-

mended to be inspected, tested, and 

maintained by a qualified Inspection 

Service in accordance with local re-

quirements and/or national codes. 

Inspection/Test Procedure 

The Model RCP-1 Panel can be in-

spected and tested without having to 

flow water into the system piping. The 

inspection and testing, in accordance 

with the requirements of NFPA 25, must 

be performed annually. 

General Inspection/Test

Step 1. 

Verify the Air Pressure Gauge 

indicates a system air pressure of 10 

to 14 psi. 

Step 2. 

Verify the Operator Interface of 

the Electronic Control only indicates a 

green light for AC Power. 

Step 3. 

Open and then close the Flow 

Test Valve. The Water Supply Gauge 

should drop to a previously noted re-

sidual pressure and then return to the 

normal static pressure. 

Step 4. 

Perform a lamp test by press-

ing and holding the ACCEPT SIGNAL 

KEY for a duration of five seconds. Ver-

ify that all system LEDs are functioning. 

Trip Test

Step 1. 

Close the System Control Valve 

and accept the supervisory alarm at the 

Operator Interface by pressing the AC-

CEPT SIGNAL KEY. 

Step 2. 

Partially open the Drain Valve 

to relieve air pressure. When the sys-

tem trips (releases), completely open 

the Drain Valve. 

• 

Note that the Operator Interface 

IDC1 indicates alarm when the air 

pressure gauge indicates nominal-

ly 8 psi. 

• 

Note that the Operator Interface indi-

cates system released. 

• 

Note that water is discharging from 

the drain line. 

Step 3. 

Reset the Model RCP-1 Pan-

el following the appropriate resetting 

instructions. 

SYSTEM PROGRAMMING MODE 

Check 

If a malfunction of the Electronic Con-

trol is suspected, verify the pre-pro-

gramming of the panel as follows: 

Step 1. 

With reference to Figure 8, re-

move the Operator Interface card and 

reinsert it so that the SYSTEM PRO-

GRAMMING MODE information listed 

on the card’s back side faces front. 

Step 2. 

Place the PROGRAM SWITCH 

(Figure 8) to the ON position and then 

momentarily press the ACCEPT SIG-

NAL KEY to accept the resulting pro-

gramming mode trouble. 

Step 3. 

Press the ACCEPT SIG-

NAL KEY to scroll through MODES 1 

through 10 and verify that the POSI-

TION 1 through 10 lights up as follows: 

• 

MODE 1: POSITION 6 for Dry Pipe

• 

MODE 1/3: POSITION 1 

• 

MODE 2: POSITION 1 for Class B Ini-

tiating Circuit Style 

• 

MODE 3: POSITION 1 for 0-Second 

Automatic Time Release Delay 

• 

MODE 4: POSITION 1 for No RAC 

Cutout Timer 

• 

MODE 5: POSITION 1 for 0 Second 

Manual Release Time Delay 

• 

MODE 6: POSITION 1 for Immediate 

Abort Release Time Delay 

• 

MODE 7: POSITION 1 for Temporal 

NAC Coding 

SYSTEM PROGRAMMING MODE

ACCEPT

SIGNAL

MODE 10

MODE 9

MODE 8

MODE 7

MODE 6

MODE 5

MODE 4

MODE 3

MODE 1

MODE 2

SIGNAL

SILENCE

SYSTEM

RESET

POSITION 10

POSITION 9

POSITION 7

POSITION 8

POSITION 6

POSITION 5

POSITION 4

POSITION 3

POSITION 1

POSITION 2

INTERFACE

CARD

ON

PROGRAM

SWITCH

FIGURE 8  

OPERATOR INTERFACE CARD (BACK SIDE)  

SYSTEM PROGRAMMING MODE

Содержание RAPID RESPONSE RCP-1

Страница 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Страница 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Страница 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Страница 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Страница 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Страница 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Страница 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Страница 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Страница 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Страница 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Страница 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Страница 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...

Отзывы: