ACM 400 S motor control unit

 

8 / 24

 

 

Warning! 

Do not connect the gate drive unit to the motor

, until you are convinced the motor 

runs  in  the 

correct  rotational  direction

 

–  e.g.  after  electrical  startup.  Otherwise 

there is a 

risk of accidents 

if the motor turns in an unexpected direction! 

Gates  without  a  mechanical  end  stop  must  be  secured  via  a  second  "safety 
limit switch" downstream of the normal limit switch, 

if the gate causes a hazard if 

the end position is exceeded,  e.g.  due to a defective limit switch. 

The  "safety limit 

switch" must be connected to the "Emergency stop”, 

which then stops the gate 

movement. slack cable switches or wicket safety devices must also be connected in 
the "Emergency stop" safety circuit. 
 

f)  Open/Closed/Stop input 

[X9]

 

 
These  control  stations  can  be  designed  as  pushbuttons,  key-operated  switches, 
coded locks or external radio buttons 

– and each as a 

make contact element

[X9.1] Connect the "Open" and "Closed" buttons to 

terminals 26...28

[X9.2] Connect the "Stop" button to 

terminals 29 / 30

.

 

"Stop"

 is a purely function input 

without safety function! 

 

Gate status 

“Open” pressed 

“Closed” pressed 

“Stop” pressed 

standing in limit position “Open“ 

closes 

standing in limit position “Closed“ 

opens 

standing in “Partly open” position 

opens 

closes 

Stands somewhere along the 
path 

opens 

closes 

opens   menu “D“ value: 

00 

Stop 

Stop 

Stop 

 

01 

Stop 

 

 

02 

Stop 

closes 

 

 

03 

closes 

 

closes   menu “D“ value: 

00 

Stop 

Stop 

Stop 

 

01 

opens 

Stop 

 

 

02 

Stop 

 

 

03 

opens 

 

“Emergency stop“ is actuated 

Automatic closing mode 

As long as it is 

pressed the gate 

remains 

permanently open 

closes, keep open 

time is ignored 

Stop, keep open 

time 

restarts 

 
The 

"Open"

 and 

"Closed"

 functions can also be actuated via channels 2 / 3 of the 

optional 

radio receiver

, as described on page 13. 

 

g) Emergency stop 

[X19]

 

 
This  can  be  realised  as  a  mushroom  button  or  wicket  safety  device,  etc.,  and  is  a 
floating 

break contact element

Connect the emergency stop button to 

terminals 38 / 39

If  you  do 

not

  want  to  connect  an  emergency  stop  button,  these  terminals  must  be 

jumpered

The "Emergency stop" function directly blocks the relay for the motor control. It is not 
possible  to  start  the  motor  via  the  dead-

man’s mode or by other inputs, as long as 

terminals 38 / 39 are interrupted. 
 

Содержание ACM 400 S

Страница 1: ...302_ACM400S_EN doc 1 24 ACM 400 S 1 motor 230V 400 gate control unit Assembly installation connection and programming instructions for the fitter Please keep these instructions in a safe place so you...

Страница 2: ...r sensors X7 11 m Method of connection for self test 11 n Speed sensor X7 11 o Photoelectric barrier X7 11 p Closing edge safety device X7 11 q Light outputs X10 12 r Universal output X12 13 s Radio r...

Страница 3: ...ta based on software status ACM400S V1 4 Parameter Symbol Limit values Units Test conditions Min Typical Max Power supply System voltage 1 230V UNetz1 205 230 255 VAC At terminals 5 8 System voltage 3...

Страница 4: ...put resistance RZUin 625 Pull Up from 5V Closed Pulse duration debounce tZU 50 ms Stop not actuated open UStop 0 4 0 5 0 V An terminals 29 0V Stop actuated closed UStop 1 0 0 1 0 V An terminals 29 0V...

Страница 5: ...s The end product manufacturer is thus responsible for compliance and declaration of CE conformity The control unit complies with the requirements in DIN EN 60204 EN 13241 1 EN 61000 6 2 EN60335 1 EN...

Страница 6: ...ating moisture X13 The weight of the control unit is approx 1 7 kg Please take this into account when choosing the type of fixing Install the control unit housing professionally at the suitable instal...

Страница 7: ...to terminals L1 3 N PE c 400V motor 3 X14 The load tap of the motor control unit and 3 phase operation is designed for a max motor output of 2000W 400V However a max operating time of 25 must not be...

Страница 8: ...0 Stop is a purely function input without safety function Gate status Open pressed Closed pressed Stop pressed standing in limit position Open closes standing in limit position Closed opens standing i...

Страница 9: ...Textmarke nicht definiert is also possible via the membrane keyboard i Universal input X8 1 With this you can realise both optional partial opening mode and Automatic closing Partial opening mode ena...

Страница 10: ...keep open time standing in partial opening position Automatically closes after expiry of the keep open time keep Open button pressed Stays open keep open time starts running again Closed button presse...

Страница 11: ...et via menu 0 X7 1 Connect the signal output to terminals 19 20 Gate status Reaction Standing running Menu 0 value 00 no sensor connected 01 Type Castalia connected If signal cannot be measured 0 5s a...

Страница 12: ...Stop 14 14 30 closes Release 15 15 31 closes opens Release if an obstruction is detected the gate moves a short distance in the opposite direction released Release time in 0 25s steps Menu B value 00...

Страница 13: ...the limit position Open along the gate s path and in the Closed limit position the signal light remains red for special functions to be switched on by radio button e g bell time switch or pulse for ga...

Страница 14: ...ive inputs outputs X6 1 At terminals 23 39 lit LEDs mean that the respective inputs have been triggered or are not closed off X6 2 At terminals 40 42 lit LEDs mean that the respective limit switch has...

Страница 15: ...t switch within 2s of starting Restart motor If error remains Gate won t move Check mechanics motor transmission emergency unlocking gate frozen Gate moves Check limit switch contact wiring or speed s...

Страница 16: ...u item appears in the display You can now use the keys to change the value as described on pages 8 16 The value is immediately adopted as soon as you set it d Reset You can reset the values to the fac...

Страница 17: ...control unit constantly performs various self tests If an error occurs the control unit is locked and an error message is displayed see table on page 15 Faulty self tests are automatically repeated a...

Страница 18: ...mergency operation In order to enable controlled movement of the gate when safety equipment closing edge safety device photoelectric barrier is continuously actuated e g in case of a defect in a safet...

Страница 19: ...pen Closed Pulse and Partial opening functions or the universal output a radio receiver can be installed in the Radio slot see page 13 X4 This is described in greater detail in the installation instru...

Страница 20: ...Stop Stop 22 OSE Stop Release 23 OSE Stop Reversing 24 OSE Release No effect 25 OSE Release Stop 26 OSE Release Release 27 OSE Release Reversing 28 OSE Reversing No effect 29 OSE Reversing Stop 30 OS...

Страница 21: ...g Stop while closing panic function 02 RADIO OPEN Stop while opening Stop while closing panic function RADIO CLOSED Reversing while opening no effect while closing 03 RADIO OPEN No effect while openin...

Страница 22: ...ACM 400 S motor control unit 22 24 13 Figures Diagrams X1 X5 X7 X8 X9 X4 X3 X2 X6...

Страница 23: ...ACM 400 S motor control unit 23 24 X10 X12 X13 X14 X17 X15 X18 X16 X19 X11...

Страница 24: ...ACM 400 S motor control unit 24 24 14 Block CIRCUIT DIAGRAM...

Отзывы: