ACM 400 S motor control unit

 

12 / 24

 

Function 

Photoelect

ric Light 

barrier 

Menu “8“ 

Safety strips 
Menu “1…4” 

8K2         OSE 

Sensor triggering 

while opening 

Sensor triggering 

whole closing 

gate at a standstill 

No effect 

No effect 

Disable sensor 

00

 

00

 

16

 

No effect 

No effect 

Stop 

01

 

01

 

17

 

No effect 

Stop 

04

 

04

 

20

 

Stop 

No effect 

05

 

05

 

21

 

Stop 

Stop 

Release *) 

02

 

02

 

18

 

No effect 

Release *) 

08

 

08

 

24

 

Release *) 

No effect 

10

 

10

 

26

 

Release *) 

Release *) 

Reversing 

03

 

03

 

19

 

No effect 

opens 

12

 

12

 

28

 

closes 

No effect 

16

 

--

 

--

 

No effect 

opens 

17

 

--

 

 

No effect 

opens 

18

 

--

 

 

No effect 

opens 

--

 

--

 

--

 

No effect 

opens 

Automatic closing after 
quitting LS 

16

 

--

 

--

 

No effect 

Closes 0.5s after 

command 

17

 

--

 

--

 

No effect 

Closes 3s after 

command 

18

 

--

 

--

 

No effect 

Closes 7s after 

command 

Combined functions 

06

 

06

 

22

 

Stop 

Release *) 

07

 

07

 

23

 

Stop 

opens 

09

 

09

 

25

 

Release *) 

Stop 

11

 

11

 

27

 

Release *) 

opens 

13

 

13

 

29

 

closes 

Stop 

14

 

14

 

30

 

closes 

Release *) 

15

 

15

 

31

 

closes 

opens 

*) Release

  =  if an obstruction is detected the gate moves a short distance in the opposite direction (released) 

Release time 
(in 0.25s steps) 

Menu “B“ value 

00 

 

….15

 

0.25s 
4.00s 

 

q) Light outputs 

[X10]

 

 
Two lamps for signal and lighting purposes can be connected for 

230V AC

, namely... 

[X10.1] at 

terminals 9 / 10

 with a load of max. 

200 W

[X10.2] at 

terminals 10 / 11

 with a load of max. 

200 W

 

Gate status 

Menu “7”value 

Light output terminals 9 / 10 

 

00

 

No light 

Gate started 

01

 

Lit time from 0   600s  

in10s steps 

 

…60

 

in limit position “Closed“ 

61

 

Light off 

in limit position “Open“ 

 

Light on 

Stopped along the path 

 

Light flashes slowly (0.5Hz) 

opens / closed 

 

Light flashes quickly (4Hz) 

When motor starts 

62

 

Short pulse  (1.5s) 

 

Gate status  

Menu 

“6“  -  value 

Warning light output terminals 10 / 11 

opens / closes 

00

 

Only while motor running 

01

 

4s before motor  while motor 

running 

02

 

10s before motor  while motor 

running 

Closes 

03

 

4s before motor  while motor 

running 

04

 

10s before motor  while motor 

running 

Содержание ACM 400 S

Страница 1: ...302_ACM400S_EN doc 1 24 ACM 400 S 1 motor 230V 400 gate control unit Assembly installation connection and programming instructions for the fitter Please keep these instructions in a safe place so you...

Страница 2: ...r sensors X7 11 m Method of connection for self test 11 n Speed sensor X7 11 o Photoelectric barrier X7 11 p Closing edge safety device X7 11 q Light outputs X10 12 r Universal output X12 13 s Radio r...

Страница 3: ...ta based on software status ACM400S V1 4 Parameter Symbol Limit values Units Test conditions Min Typical Max Power supply System voltage 1 230V UNetz1 205 230 255 VAC At terminals 5 8 System voltage 3...

Страница 4: ...put resistance RZUin 625 Pull Up from 5V Closed Pulse duration debounce tZU 50 ms Stop not actuated open UStop 0 4 0 5 0 V An terminals 29 0V Stop actuated closed UStop 1 0 0 1 0 V An terminals 29 0V...

Страница 5: ...s The end product manufacturer is thus responsible for compliance and declaration of CE conformity The control unit complies with the requirements in DIN EN 60204 EN 13241 1 EN 61000 6 2 EN60335 1 EN...

Страница 6: ...ating moisture X13 The weight of the control unit is approx 1 7 kg Please take this into account when choosing the type of fixing Install the control unit housing professionally at the suitable instal...

Страница 7: ...to terminals L1 3 N PE c 400V motor 3 X14 The load tap of the motor control unit and 3 phase operation is designed for a max motor output of 2000W 400V However a max operating time of 25 must not be...

Страница 8: ...0 Stop is a purely function input without safety function Gate status Open pressed Closed pressed Stop pressed standing in limit position Open closes standing in limit position Closed opens standing i...

Страница 9: ...Textmarke nicht definiert is also possible via the membrane keyboard i Universal input X8 1 With this you can realise both optional partial opening mode and Automatic closing Partial opening mode ena...

Страница 10: ...keep open time standing in partial opening position Automatically closes after expiry of the keep open time keep Open button pressed Stays open keep open time starts running again Closed button presse...

Страница 11: ...et via menu 0 X7 1 Connect the signal output to terminals 19 20 Gate status Reaction Standing running Menu 0 value 00 no sensor connected 01 Type Castalia connected If signal cannot be measured 0 5s a...

Страница 12: ...Stop 14 14 30 closes Release 15 15 31 closes opens Release if an obstruction is detected the gate moves a short distance in the opposite direction released Release time in 0 25s steps Menu B value 00...

Страница 13: ...the limit position Open along the gate s path and in the Closed limit position the signal light remains red for special functions to be switched on by radio button e g bell time switch or pulse for ga...

Страница 14: ...ive inputs outputs X6 1 At terminals 23 39 lit LEDs mean that the respective inputs have been triggered or are not closed off X6 2 At terminals 40 42 lit LEDs mean that the respective limit switch has...

Страница 15: ...t switch within 2s of starting Restart motor If error remains Gate won t move Check mechanics motor transmission emergency unlocking gate frozen Gate moves Check limit switch contact wiring or speed s...

Страница 16: ...u item appears in the display You can now use the keys to change the value as described on pages 8 16 The value is immediately adopted as soon as you set it d Reset You can reset the values to the fac...

Страница 17: ...control unit constantly performs various self tests If an error occurs the control unit is locked and an error message is displayed see table on page 15 Faulty self tests are automatically repeated a...

Страница 18: ...mergency operation In order to enable controlled movement of the gate when safety equipment closing edge safety device photoelectric barrier is continuously actuated e g in case of a defect in a safet...

Страница 19: ...pen Closed Pulse and Partial opening functions or the universal output a radio receiver can be installed in the Radio slot see page 13 X4 This is described in greater detail in the installation instru...

Страница 20: ...Stop Stop 22 OSE Stop Release 23 OSE Stop Reversing 24 OSE Release No effect 25 OSE Release Stop 26 OSE Release Release 27 OSE Release Reversing 28 OSE Reversing No effect 29 OSE Reversing Stop 30 OS...

Страница 21: ...g Stop while closing panic function 02 RADIO OPEN Stop while opening Stop while closing panic function RADIO CLOSED Reversing while opening no effect while closing 03 RADIO OPEN No effect while openin...

Страница 22: ...ACM 400 S motor control unit 22 24 13 Figures Diagrams X1 X5 X7 X8 X9 X4 X3 X2 X6...

Страница 23: ...ACM 400 S motor control unit 23 24 X10 X12 X13 X14 X17 X15 X18 X16 X19 X11...

Страница 24: ...ACM 400 S motor control unit 24 24 14 Block CIRCUIT DIAGRAM...

Отзывы: