ACM 400 S motor control unit 

 

 

11 / 24 

l)  Power supply for sensors 

[X7]

 

 
for the sensors power supply are available: 

  24V~ /0,2A at terminal 21 
  12V= /0,1A at terminal 22 

each applied against the 0V connection at terminal 20. 
 

m) Method of connection for "self-test" 

The 

receiver  side 

of  the  photoelectric  barrier  or  the  8K2  safety  strips  are  tested 

during self-test by 

short interruption 

of the

 

0V connections (earthing). 

You can also include the 

transmitter side

 in the self-test 

– by 

supply it with power

 

via the universal output (see page 13). 
 

n) Speed sensor 

[X7]

 

 

  The  speed  sensor  monitors  running  of  the  motor.  If  a  sensor  signal  remains  off 

although the motor has been started, the control unit stops the motor running with 
the  error  message  E2,  as  either  the  sensor  is  defective  or  a  motor/transmission 
break exists. 

  Obstruction / limit position detection via the speed sensors is not possible. 

 

The type of speed sensor is set via menu “0”.

 

 [X7.1] Connect the 

signal output

 to 

terminals 19 / 20

 

Gate status 

Reaction 

Standing 

running        

Menu “

0

“ – value:  00

  

no sensor connected 

 

01  Type "Castalia" connected 

If signal cannot be measured 0.5s 
after motor starts: “Stop“ until next 
command input 

 

02  Type "DSLTA-51" connected 

 

03  Type "FACT" connected 

 

o) Photoelectric barrier 

[X7]

 

 
You  can  connect  photoelectric  barriers,  DWG  strips,  ground  loops,  etc.  as  floating 

break contact elements 

to monitor the space within which the gate moves. 

[X7.2] Connect a 

photoelectric barrier

 to 

terminals 30 / 31

If  you  do  not  want  to  connect 

any  photoelectric  barrier

,  the  terminals  must  be 

jumpered 

or 

disabled

 

p) Closing edge safety device 

[X7]

 

 
4 safety strips can be connect to the control unit as closing edge safety devices, e.g. 
Type "8K2" or "-OSE".  
[X7.3] Connect the safety strips 1...4 to terminals 32...37. 
If  using  "8K2"  strips,  the  outer  surround  of  the  safety  strip  must  be  connected  to 
terminal 33 and/or 36 (0V). 
Any unused inputs must be 

jumpered with 8.2 kohl 

or 

disabled

OSE connection:  

+12V 

terminal 22 (brown cable), 

 

0V 

terminal 20 (white cable) 

 

Signal  terminal 32, 34, 35, 37 (green cable) 

Содержание ACM 400 S

Страница 1: ...302_ACM400S_EN doc 1 24 ACM 400 S 1 motor 230V 400 gate control unit Assembly installation connection and programming instructions for the fitter Please keep these instructions in a safe place so you...

Страница 2: ...r sensors X7 11 m Method of connection for self test 11 n Speed sensor X7 11 o Photoelectric barrier X7 11 p Closing edge safety device X7 11 q Light outputs X10 12 r Universal output X12 13 s Radio r...

Страница 3: ...ta based on software status ACM400S V1 4 Parameter Symbol Limit values Units Test conditions Min Typical Max Power supply System voltage 1 230V UNetz1 205 230 255 VAC At terminals 5 8 System voltage 3...

Страница 4: ...put resistance RZUin 625 Pull Up from 5V Closed Pulse duration debounce tZU 50 ms Stop not actuated open UStop 0 4 0 5 0 V An terminals 29 0V Stop actuated closed UStop 1 0 0 1 0 V An terminals 29 0V...

Страница 5: ...s The end product manufacturer is thus responsible for compliance and declaration of CE conformity The control unit complies with the requirements in DIN EN 60204 EN 13241 1 EN 61000 6 2 EN60335 1 EN...

Страница 6: ...ating moisture X13 The weight of the control unit is approx 1 7 kg Please take this into account when choosing the type of fixing Install the control unit housing professionally at the suitable instal...

Страница 7: ...to terminals L1 3 N PE c 400V motor 3 X14 The load tap of the motor control unit and 3 phase operation is designed for a max motor output of 2000W 400V However a max operating time of 25 must not be...

Страница 8: ...0 Stop is a purely function input without safety function Gate status Open pressed Closed pressed Stop pressed standing in limit position Open closes standing in limit position Closed opens standing i...

Страница 9: ...Textmarke nicht definiert is also possible via the membrane keyboard i Universal input X8 1 With this you can realise both optional partial opening mode and Automatic closing Partial opening mode ena...

Страница 10: ...keep open time standing in partial opening position Automatically closes after expiry of the keep open time keep Open button pressed Stays open keep open time starts running again Closed button presse...

Страница 11: ...et via menu 0 X7 1 Connect the signal output to terminals 19 20 Gate status Reaction Standing running Menu 0 value 00 no sensor connected 01 Type Castalia connected If signal cannot be measured 0 5s a...

Страница 12: ...Stop 14 14 30 closes Release 15 15 31 closes opens Release if an obstruction is detected the gate moves a short distance in the opposite direction released Release time in 0 25s steps Menu B value 00...

Страница 13: ...the limit position Open along the gate s path and in the Closed limit position the signal light remains red for special functions to be switched on by radio button e g bell time switch or pulse for ga...

Страница 14: ...ive inputs outputs X6 1 At terminals 23 39 lit LEDs mean that the respective inputs have been triggered or are not closed off X6 2 At terminals 40 42 lit LEDs mean that the respective limit switch has...

Страница 15: ...t switch within 2s of starting Restart motor If error remains Gate won t move Check mechanics motor transmission emergency unlocking gate frozen Gate moves Check limit switch contact wiring or speed s...

Страница 16: ...u item appears in the display You can now use the keys to change the value as described on pages 8 16 The value is immediately adopted as soon as you set it d Reset You can reset the values to the fac...

Страница 17: ...control unit constantly performs various self tests If an error occurs the control unit is locked and an error message is displayed see table on page 15 Faulty self tests are automatically repeated a...

Страница 18: ...mergency operation In order to enable controlled movement of the gate when safety equipment closing edge safety device photoelectric barrier is continuously actuated e g in case of a defect in a safet...

Страница 19: ...pen Closed Pulse and Partial opening functions or the universal output a radio receiver can be installed in the Radio slot see page 13 X4 This is described in greater detail in the installation instru...

Страница 20: ...Stop Stop 22 OSE Stop Release 23 OSE Stop Reversing 24 OSE Release No effect 25 OSE Release Stop 26 OSE Release Release 27 OSE Release Reversing 28 OSE Reversing No effect 29 OSE Reversing Stop 30 OS...

Страница 21: ...g Stop while closing panic function 02 RADIO OPEN Stop while opening Stop while closing panic function RADIO CLOSED Reversing while opening no effect while closing 03 RADIO OPEN No effect while openin...

Страница 22: ...ACM 400 S motor control unit 22 24 13 Figures Diagrams X1 X5 X7 X8 X9 X4 X3 X2 X6...

Страница 23: ...ACM 400 S motor control unit 23 24 X10 X12 X13 X14 X17 X15 X18 X16 X19 X11...

Страница 24: ...ACM 400 S motor control unit 24 24 14 Block CIRCUIT DIAGRAM...

Отзывы: