14
Operative Instructions
supply taps, drain and anything else needed.
- These components should have all the needed
features and should be installed at the locations
shown in the installation scheme.
a
WARNING! The use of unsuitable parts,
and/or the implementation of installation
procedures other than those shown on the
installation diagram, will immediately void
the machine warranty.
- The characteristics of the electricity network must
be compatible with the values required for correct
operation indicated on the machine identification
plate and on the technical data sheet.
- The machine must be connected to an efficient
earthing system (according to electrical safety
standards).
Ö
IMPORTANT NOTE! The manufacturer is not
to be held liable for any damage caused by
improper grounding of the machine or faulty
power supply.
5.1 Under the counter installation
0.2" / 50 mm
0.07
" /
2,5 mm
0.07
" /
2,5 mm
Fig. 7
The under the counter machine can be inserted under
a continuous worktop or under the sink’s drip surface.
The recess niche must have a minimum space as shown
in Fig. 7.
The presence of adequate air intakes must be
guaranteed to allow the ventilation of the area behind
the machine, in order to avoid creating a closed space
without exchange of air with the room environment.
5.2 Electrical connection
c
HAZARD! Only qualified and experienced
personnel can connect the machine to the
mains supply, in compliance with the current
laws and regulations.
a
WARNING! In the single-phase version, the
main switch of the power supply line must be
a multi-pole circuit breaker, with adequate
residual current protection.
a
WARNING! In the three-phase version,
the main switch must be multi-pole circuit
breaker, with adequate residual current
protection, positioned near the machine and
not covered by machines or other that may
hinder its use.
- The magnetic-snap safety system, or the fuses, must
be calibrated according to the power indicated on the
machine plate.
- Make sure that the measured voltage is equal to
the one reported on the identification plate of the
machine;
- Check that the voltage does not differ by more than
10% from its rated value;
- Make sure that the electrical system is equipped with
an efficient grounding connection;
- Connect the cable that comes out of the machine
to the wall socket. In case the machine has a three-
phase connection (standard), connect the cable
installed on the machine to the three-phase plug
and insert it into the interlocked socket next to the
machine (not provided).
- The socket must be accessible after the machine
installation. This facilitates verification of the electrical
safety, e.g. in repair or maintenance interventions.
- The machine must be supplied with current whose
voltage, frequency and protection values correspond
to those indicated on the data plate.
- Additional indications regarding the electrical
connection are shown in the installation plan.
Ö
IMPORTANT NOTE! The fuses must be in
compliance with Standards IEC 60127-2,
UL248-14, CSA C22.2.