![TSUJI ELECTRONICS PM16C-16 Скачать руководство пользователя страница 74](http://html1.mh-extra.com/html/tsuji-electronics/pm16c-16/pm16c-16_user-manual_1178501074.webp)
Local
Command
Command description
(Auto change scan
command)
ACSxyyy/PNT/JJJ
・・
J/FNC/LLL
・・
L
set data command
x :channnel 0,1,2,
・・・
,9,A,B,C,D,E,F
yyy:sequence number 0 to 127max
PNT:END should be written at next to end seq.
:ADD relative address from start point
:TIM relative time from previous point
:ACC speed data while accelerration
:DEC speed data while deceleration
JJJ:relative address ±2,147,483,647max
:time 0 to 65,535ms
FNC:SPD LLL
・・・
L means speed data in pps
:RTE LLL
・・・
L means rat data
:SLW slow stop
:FST fast stop
:NOP no operation(skip this seq. number)
LLL:speed 1 to 5,000,000pps
:rate rate data number in the same range
ABSx(B)±ddd...
RELx(B)±ddd...
SCANPx
SCANNx
auto change scan start command when the axis is
auto change scan ready
○
ACS?xyyy
data read command
x :channnel 0,1,2,
・・・
,9,A,B,C,D,E,F
yyy:sequence number 0 to 127max
reply: xyyy/PNT/JJJ
・・・
J/FNC/LLL
・・・
L
ACSCx
auto change scan ready clear command
○
ACSH?x
reply aabb,hhhh,hhhh
aa:code(00:SPD,01:RTE,02:SLW,03:FST,0F:NOP)
bb:sequence number(0 to 7F)
hh
・・・
hh:data
○
ACSP?x
auto change scan ready read command
reply:ready, not ready
ACSPx
auto change scan ready set command
○
ACSK?x
reply aabb,hhhh,hhhh
aa:code(00:END,01:ADD,02:TIM,80:ACC,81:DEC)
bb:sequence number(0 to 7F)
hh
・・・
hh:data
○
VER?
read version reply:1.00 13-05-14 PM16C-16
○
VERH?
hardware version read reply:HD-VER0,1,2,5,6
○
FROM?
current FROM read reply:FROM0,FROM1
FROM0, FROM1
FROM select
○
ERR?
Error status read
reply: NO ERROR/MCC06 BUSY ERROR etc.
○
ERRF?
Error status flag read
reply: H b3: OTHER ERROR b2: PARAMETER ERROR
b1: MCC06 BUSY ERROR b0: COMMAND ERROR
○
ERRC
all error flag clear.
○
ERRCx
paticular error flag clear.
x: 3: OTHER ERROR 2: PARAMETER ERROR
1: MCC06 BUSY ERROR 0: COMMAND ERROR
○
STSM?
read status port1 of MCC06 aaaa/bbbb/cccc/dddd
REST
restart without power off-on