49
2.
3.
In the case of pulse, the motor is moved on the outside of the start and end points of
the timing signal.
Please move to the CCW side than the starting point if you want to observe the pulse
in the move to the CW. And also, please move to the CW side than the starting point
if you want to observe the pulse in the move to the CCW.
If the gate, you do not need this operation.
4.
Prepare the timing signal output.
In local mode, please add "#" to the appropriate channel on motor drive screen
(page 13). In remote mode, please enter the following command.
Command TMG<md><ch><data>
Set the timing signal start point and end point.
Argument
<md>
mode
S/ set start point E/ set end point
<data>
start/end point
-2,147,483,647 ~ +2,147,483,647
Initial value Start point: +1,000 end point: +10,000
Reply Nothing
Example
TMGS2+10000
CH2’s timing signal start point will be set to 10,000.
TMGE2+50000
CH2’s timing signal end point will be set to 50,000.
Remarks Only remote mode
Command TMG<md><ch>
Set / clear the timing signal output preparation mode.
Argument <md>
state
R/ Ready C/ Clear
Initial value Clear
Reply Nothing
Example TMGR0
Make the timing signal output preparation of ch0.
Remarks Only remote mode
Command TMGR?<ch>
Confirm the timing signal output preparation mode.
Reply
YES/ The timing signal output preparation mode is ready.
NO/ The timing signal output preparation mode is not ready.
Example TMGR?F reply: NO
Remarks