T
ec
hn
ic
al
S
ec
tio
n
2
7
CONTROL MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
TEMPERATURE
SENSITIVITY
TEMP DB
The
TEMP DB
item determines the controller’s temperature
control deadband, which is defined as the temperature range
above
and
below the temperature set point (
TEMP SETP
),
where the controller will not take corrective action.
65
66
67
68
69
70
71
72
73
74
75
0
15
30
45
60
Time
T
em
p
er
at
u
re F
If
TEMP
DB
is set to ±1.0
°
F, and the
TEMP
SETP
is set to
70.0
°
F, the controller will not take corrective action unless the
space temperature is below 69.0
°
F or above 71.0
°
F.
±0.0
°
F to ±1.0
°
F
±
0.3
°
F