80
Appendix B
Supported Commands
Command Response
Request Device ID
Returns 0x10
Synchronize Time Command
Acknowledged. There Is No Internal Clock To
Synchronize.
Poll Without/With Ack Message
Any Change Of Status Is Returned
Read Analog Input Command
Variable Value
Read Binary Input Command
Variable Value
Read Analog Output Command
Variable Value
Write Analog Input
Acknowledge
Write Binary Input
Acknowledge
Write Analog Output
Acknowledge
Override Analog Input Command
Acknowledge
Override Binary Input Command
Acknowledge
Override Analog Output Command
Acknowledge
Override Release Request
Acknowledge
Identify Device Type Command
Returns 0x10h
Note
: Poll Without/With Ack Message will need to be sent twice in order to receive all of the possible change of
status variables.
Variable Map
NPT NPA UNITS
i
DESCRIPTION
AI
1
ft/min, m/s, in.
H
2
O, Pa
Room Pressure Value
AI
2
CFM, l/s
Current Offset
AI 3
°
F,
°
C
Current Temperature
AI
4
CFM, l/s
Minimum Supply Set point
AI
5
CFM, l/s
Total Hood Exhaust
AI
6
CFM, l/s
Total Auxiliary Exhaust
AI
7
CFM, l/s
Total Supply
AI
8
CFM, l/s
Total Exhaust
AI
9
CFM, l/s
Hood 1 Flow
AI
10
CFM, l/s
Hood 2 Flow
AI
11
CFM, l/s
Hood 3 Flow
AI
12
CFM, l/s
Hood 4 Flow
AI
13
CFM, l/s
Hood 5 Flow
AI
14
CFM, l/s
Hood 6 Flow
AI
15
CFM, l/s
Hood 7 Flow
AI
16
CFM, l/s
Auxiliary Exhaust 1 Flow
AI
17
CFM, l/s
Auxiliary Exhaust 2 Flow
AI
18
CFM, l/s
Supply 1 Flow
AI
19
CFM, l/s
Supply 2 Flow
AI
20
CFM, l/s
Supply 3 Flow
AI
21
CFM, l/s
Supply 4 Flow
AI
22
%
Supply Control Output
AI
23
%
Exhaust Control Output
AI
24
%
Temp. Control Output
BI
1
Low Pressure Alarm
0=Normal
1=Low
Alarm
BI
2
High Pressure Alarm
0=Normal
1=High
Alarm