DIAGNOSTICS MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
SENSOR
COMMUNICATION
SENSOR
STAT
The
SENSOR STAT
item verifies that the RS-485 communications between the pressure sensor and DIM is
working correctly. Pressure sensor error messages do not display on DIM except when
SENSOR STAT
item is
selected. This item displays NORMAL if communications are established correctly. If problems exist, one of four
error messages will display:
COMM ERROR
- DIM cannot communicate with sensor. Check all wiring and pressure sensor address. Address
must be 1.
SENS ERROR
- Problem with sensor bridge. Physical damage to pressure sensor or sensor circuitry. Unit is not
field repairable. Send to TSI for repair.
CAL ERROR
- Calibration data lost. Sensor must be returned to TSI to be calibrated.
DATA ERROR
- Problem with EEPROM, field calibration, or analog output calibration lost. Check all data
programmed and confirm unit is function correctly.
TEMPERATURE
INPUT
TEMP INPUT
The
TEMP INPUT
item reads the input from the temperature sensor. When this item is entered, a voltage will be
indicated on the display. The exact voltage displayed is relatively unimportant. It is more important that the voltage
changes, indicating the temperature sensor is working correctly. The output range that can be read is resistance.
UNOCCUPY SET
INPUT
OCCUPANT
SWT
The
OCCUPANT SWT
item reads the input of the
OCCUPANT SWT
contact pins 11 and 12 (DIM). When this
item is entered, the display will indicate either open or closed. If the display indicates open, the AOC uses the
VENT MIN SET
or
COOLING FLOW
as the minimum supply flow set point. If the display indicates closed, the
AOC uses
UNOCCUPY SET
as the minimum supply flow set point. The AOC will use the
SET POINT
pressure
set point in either case.