SUPPLY FLOW MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
MAXIMUM FLOW
STATION
VELOCITY
TOP
VELOCITY
The
TOP VELOCITY
item is used to input the maximum
velocity of a linear flow station output. A
TOP VELOCITY
must be input for the linear flow station to operate.
NOTE
: This item is disabled if a pressure based flow station
is installed.
0–5,000 FT/MIN
(0–25.4 m/s)
0
SUPPLY FLOW
LOW
CALIBRATION
SETTING
SP LOW
SETP
The
SP LOW SETP
menu item sets the supply damper
position for supply low flow calibration.
0% Open to 100% Open
0% OPEN
SUPPLY FLOW
HIGH
CALIBRATION
SETTING
SP HIGH
SETP
The
SP HIGH SETP
menu item sets the supply damper
position for the supply high flow calibration.
0% Open to 100% Open
100% OPEN
SUPPLY FLOW
LOW
CALIBRATION
SP1 LOW
CAL
through
SP4 LOW
CAL
The
SP# LOW CAL
menu items display the currently
measured supply flow rate and the calibrated value for that
supply flow. The supply dampers will move to the
SP LOW
SETP
damper position for the low calibration. The calibrated
supply flow can be adjusted using the
S
/
T
keys to make it
match a reference measurement. Pressing the
SELECT
key
will save the new calibration data.
SUPPLY FLOW
HIGH
CALIBRATION
SP1 HIGH
CAL
through
SP4 HIGH
CAL
The
SP# HIGH CAL
menu items display the currently
measured supply flow rate and the calibrated value for that
supply flow. The supply dampers will move to the
SP HIGH
SETP
damper position for the low calibration. The calibrated
supply flow can be adjusted using the
S
/
T
keys to make it
match a reference measurement. Pressing the
SELECT
key
will save the new calibration data.