18
Part Two
ALARM MENU
(continued)
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
MINIMUM
SUPPLY FLOW
ALARM
MIN SUP
ALM
The
MIN SUP ALM
item sets the supply flow alarm set point. A
minimum flow alarm is defined as when the supply duct flow is
less than the
MIN SUP ALM
set point.
NOTE
: Supply air duct size(s)
SP# DCT AREA
(Supply Flow
menu) must be entered before
MIN SUP ALM
can be
accessed. Actual total supply air flow is found in
TOT
SUP FLOW
menu item (system flow menu).
WIRING: This item is disabled when the
UNOCCUPY SET
is
enabled [SWITCH INPUT contact closure is
closed
(pins 11 and 12, DIM), or the RS 485 communications
sends a command].
0-29,950 CFM
(0-14,125 l/s)
Linear based flow
stations 0 to
TOP
VELOCITY
times the
supply duct area in
square feet (ft
2
): square
meters (m
2
).
OFF
MAXIMUM
EXHAUST FLOW
ALARM
MAX EXH
ALM
The
MAX EXH ALM
item sets the general exhaust duct’s flow
alarm set point. A maximum flow alarm is defined as when the
general exhaust duct flow is greater than the
MAX EXH ALM
set
point.
NOTE
: General exhaust air duct size
EX1 DCT AREA
and / or
EX2 DCT AREA
(Exhaust Flow menu) must be entered
before
MAX EXH ALM
can be accessed.
Actual total
exhaust air
flow is found in
TOT EXH FLOW
menu
item (SYSTEM FLOW menu).
0-30,000 CFM
(0-14,100 l/s)
Linear based flow
stations 0 to
TOP
VELOCITY
times the
supply duct area in
square feet (ft
2
): square
meters (m
2
).
OFF
ALARM RESET
ALARM
RESET
The
ALARM RESET
item selects how the alarms terminate after
the unit returns to control set point (pressure or flow).
UNLATCHED
(alarm follow) automatically resets the alarms
when the unit reaches control set point.
LATCHED
requires the
staff to press the
RESET
key after the unit returns to control set
point. The
ALARM RESET
affects the audible alarm, visual
alarm, and relay output, which means all are latched or unlatched.
LATCHED
OR
UNLATCHED
UNLATCHED