30
Part Two
SYSTEM FLOW MENU
MENU ITEM
SOFTWARE
NAME ITEM
DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
TOTAL SUPPLY
AIR FLOW
TOT SUP
FLOW
The
TOT SUP FLOW
menu item displays the current total
measured supply flow into the laboratory. This item calculates
total supply by summing
SP1 FLOW IN
though
SP4 FLOW
IN
. This is a system information only menu item; no
programming is possible.
NONE: Read only
value
NONE
TOTAL EXHAUST
AIR FLOW
TOT EXH
FLOW
The
TOT EXH FLOW
menu item displays the current total
measured exhaust flow out of the laboratory. This item
calculates total exhaust by summing
EX1 FLOW IN,
EX2
FLOW IN,
and
HD1 FLOW IN
through
HD7 FLOW IN
. This
is a system information only menu item; no programming is
possible.
NONE: Read only
value
NONE
CONTROL OFFSET
VALUE
OFFSET
VALUE
The
OFFSET VALUE
menu item displays the actual flow
offset being used to control the laboratory. The
OFFSET
VALUE
is calculated by the AOC control algorithm, which uses
the
MIN OFFSET, MAX OFFSET
, and
SET POINT
items to
calculate required offset. This is a system information only
menu item: no programming is possible.
NONE: Read only
value
NONE
SUPPLY FLOW SET
POINT
(CALCULATED)
SUP SET
POINT
The
SUP SET POINT
menu item displays the supply flow set
point, which is calculated by the AOC control algorithm. The
calculated
SUP SET POINT
is a diagnostic item used to
compare the actual
TOT SUP FLOW
to the calculated flow
(they should match within 10%). This is a system information
only menu item: no programming is possible.
NONE: Read only
value
NONE