Interface connections
Component
Connection
Job
X-CUBE Control
Bus
black cable with black M12 plug
connection
Lighting
grey cable with black M12 plug
connection
M12 plug connections
Plug the connectors together straight
and tighten by hand. Then tighten
the screw connections by 90° with
the open-end spanners (securing
against working loose).
X-CUBE Control sensors
Anti-frost thermostat
black cable with black 3-pin M8
plug connection
Duct smoke detector 1
black cable with black 4-pin plug
connection
Duct smoke detector 2
black cable with red 4-pin plug
connection
M8 plug connector
Plug M8 plug connections together
straight.
Fans with < 13 A power consumption
are pluggable.
5-pin power plug connector
plug together straight and close
retainer (protection against working
loose).
Fans > 13 A, double fans or fan
arrays
No discontinuities, rolled-up cables
Route the cables through the
intended cable routes and connect
them to the switch cabinet according
to the circuit diagram.
Rotary heat exchanger
3-pin power plug connector
plug together straight and close
retainer (protection against working
loose).
Shut-off dampers with spring return
actuator torque > 20 Nm
No discontinuities, rolled-up cables
Route the cables through the
intended cable routes and connect
them to the switch cabinet according
to the circuit diagram.
None of the other regulation and control components are designed to be pluggable. The rolled-up cables must be
routed through the intended cable routes and connected to the switch cabinet according to the circuit diagram.
Installation
Wiring
Air handling unit X-CUBE X2 / X-CUBE X2 compact
42