DampPosMinValue_VE
BMS access: RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller in the system with the widest
closed damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-86 –
value and event state
Modbus: Register 121 (value) and register 122
(event state)
DampPosMaxValue_VS
BMS access: RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the widest open damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-87 –
value and event state
Modbus: Register 123 (value) and register 124
(event state)
DampPosMinValue_VS
BMS access: RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller in the system with the widest
closed damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-88 –
value and event state
Modbus: Register 125 (value) and register 126
(event state)
DampPosMaxValue_PKE
BMS access: RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the extract
air pressure controller in the system with the widest
open damper blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-89 –
value and event state
Modbus: Register 127 (value) and register 128
(event state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
68