DampPosMin_TE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard, extract air or room extract air controller
with the least wide open damper blade
1, 3, 5
For the evaluation of the damper blade positions in
the extract air system (1 fan) for fume cupboard and
room extract air
For UNIVERSAL:
output of the damper blade posi-
tion of the extract air room pressure controller in the
system with the widest closed damper blade
1, 3, 4
Data point
BACnet: Analog Value Object – Instance AV-16 –
value and event state
Modbus: Register 25 (value) and register 26 (event
state)
DampPosMax_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the widest open damper
blade
1, 4
Data point
BACnet: Analog Value Object – Instance AV-17 –
value and event state
Modbus: Register 27 (value) and register 28 (event
state)
DampPosMin_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit:
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the least wide open
damper blade
1, 5
Data point
BACnet: Analog Value Object – Instance AV-18 –
value and event state
Modbus: Register 29 (value) and register 30 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
65