
PressAct
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the differential pressure control actual
value within the system
The actual value is recorded by a differential pres-
sure transducer connected to the RR with RMF or to
the TAM with RMF.
Data point
BACnet: Analog Value Object – Instance AV-6
Modbus: Register 11
VelocitySet
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Unit: m/s
Function
Output of the face velocity setpoint value if the fume
cupboard controller is equipped with a face velocity
transducer (FH-VS)
Data point
BACnet: Analog Value Object – Instance AV-7
Modbus: Register 6
VelocityAct
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Unit: m/s
Function
Output of the face velocity actual value if the fume
cupboard controller is equipped with a face velocity
transducer (FH-VS)
Data point
BACnet: Analog Value Object – Instance AV-8
Modbus: Register 5
WireSensorPos
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the sash position of the fume cupboard as
a percentage value between the closed position
(0 %) and the open position (100 %)
(Applies only if the fume cupboard controller is
equipped with a sash distance sensor (FH-DS, FH-
DV, FH-VD))
Data point
BACnet: Analog Value Object – Instance AV-9
Modbus: Register 34
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
54
Содержание EM-IP
Страница 7: ...Security Environmental protection Expansion module EM IP 7...
Страница 78: ...Expansion module EM IP 78...
Страница 79: ...Expansion module EM IP 79...