DampPosMinState_TE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the fume cupboard, extract
air or room extract air controller with the least wide
open damper blade
5
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Multistate Value Object – Instance MV-16
Modbus: Register 26
DampPosMaxState_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the room supply air controller
with the widest open damper blade
4
Data point
BACnet: Multistate Value Object – Instance MV-17
Modbus: Register 28
DampPosMinState_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the room supply air controller
with the least wide open damper blade
5
Data point
BACnet: Multistate Value Object – Instance MV-18
Modbus: Register 30
DampPosMaxState_EC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the extract air controller with
the widest open damper blade
4
Data point
BACnet: Multistate Value Object – Instance MV-26
Modbus: Register 50
DampPosMinState_EC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Equipment function: FH, RR, RR with RMF, EC, SC,
TAM, TAM with RMF
Function
Output of the status of the extract air controller with
the least wide open damper blade
5
Data point
BACnet: Multistate Value Object – Instance MV-27
Modbus: Register 52
DampPosMaxState_SC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the supply air controller with
the widest open damper blade
4
Data point
BACnet: Multistate Value Object – Instance MV-28
Modbus: Register 54
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP