DO*_SetByLocal (BACnet), DO_SetByLocal
(Modbus)
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Feedback from the controller about switch outputs
DO1 … DO6 used by the controller or adapter
module
Data point
BACnet:
Binary Value Object – Instance BV-25 (DO1_Setby-
Local) – Instance BV-30 (DO6_SetbyLocal)
–
0 = output inactive
–
1 = output active
Modbus:
Register 62, bit 0 (DO1_Set) – bit 5 (DO6_Set)
–
Bit not set = output inactive
–
Bit set = output active
LocalAlarm_*
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of the local alarm of the bus user, addressed
by device ID, i.e. ID 4
ð
LocalAlarm_3
Data point
BACnet:
Binary Value Object – Instance BV-31 (LocalA-
larm_0) – Instance BV-54 (LocalAlarm_23)
–
0 = No alarm
–
1 = Alarm
Modbus:
Register 63 - bit 0 (LocalAlarm_0) – bit 7 (LocalA-
larm_7)
Register 64 - bit 0 (LocalAlarm_8) – bit 7 (LocalA-
larm_15)
Register 65 - bit 0 (LocalAlarm_16) – bit 7 (LocalA-
larm_23)
–
Bit not set = inactive
–
Bit set = active
DampPosMaxState_FH
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Function
Output of the status of the fume cupboard controller
with the widest open damper blade
4
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Multistate Value Object – Instance MV-11
Modbus: Register 16
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
58