SystemDevices
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Number of identified EASYLAB system components
Data point
BACnet: Analog Value Object – Instance AV-21
Modbus Register 37
SC_GetPos
Equipment function: not available
Device_ID_*
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of the Device ID of the device being
addressed (0 – 23)
The Device_ID_* data points (0 – 23) of the EM-IP
expansion module contain the Device ID of each
controller (1 – 24)
Controllers are automatically assigned a Device ID
as part of the configuration procedure
Controllers are automatically assigned to the data
points
Example
–
A controller has Device ID 5
–
The device with device ID 5 is automatically
assigned to VolflowAct_4 and LocalAlarm_4.
–
Devices with device ID 0 are not displayed.
–
If the device ID is assigned twice, an error mes-
sage is displayed in the web interface.
Data point
BACnet: Analogue Value Object – Instance AV-32
(Device_ID_0) – Instance AV-55 (Device_ID_23)
Modbus Register 37
VolflowAct_*
BMS access: RD
Equipment function: FH, RR, RR with RMF, EC, SC,
TAM, TAM with RMF
Unit: l/s
Function
Output of the volume flow rate actual value of the
bus user, addressed by device ID, i.e. device ID4
ð
VolflowAct_3
Data point
BACnet: Analogue Value Object – Instance AV-56
(VolFlowAct_0) – Instance AV-79 (VolFlowAct_23)
Modbus: Register 90 (VolFlowAct_0) – 113 (VolFlo-
wAct_23)
Interface information
Data points – detailed description > Output variables
Expansion module EM-IP
55