background image

13R

Service

Before returning your Inverter/Charger for service, follow these steps: 1.) Review the installation and operation instructions to ensure that
the service problem does not originate from a misreading of the instructions. Also, check that the circuit breaker(s) are not tripped.* 2.) If
the problem continues, do not contact or return the Inverter/Charger to the dealer. Instead, call Tripp Lite at (773) 869-1233. A service tech-
nician will ask for the Inverter/Charger’s model number, serial number and purchase date and will attempt to correct the problem over the
phone. 3.) If the problem requires service, the technician will issue you a Returned Material Authorization (RMA) number, which is
required for service. Securely pack the Inverter/Charger to avoid damage during shipping. Do not use Styrofoam beads for packaging.**
Any damages (direct, indirect, special, incidental or consequential) to the Inverter/Charger incurred during shipment to Tripp Lite or an
authorized Tripp Lite service center is not covered under warranty. Inverter/Chargers shipped to Tripp Lite or an authorized Tripp Lite serv-
ice center must have transportation charges prepaid. Mark the RMA number on the outside of the package. If the Inverter/Charger is with-
in the warranty period, enclose a copy of your sales receipt. Return the Inverter/Charger for service using an insured carrier to the address
given to you by the Tripp Lite service technician.

* This is a common cause of service inquiries which can be easily remedied by following the resetting instructions in this manual. ** If you require packaging, the technician can arrange to send you proper packaging.

Your Inverter/Charger requires no maintenance and contains no user-serviceable or replaceable parts, but should be kept dry at all times.
Periodically check, clean and tighten all cable connections, as necessary, both at the unit and at the battery.

Maintenance

Troubleshooting

SYMPTOM

PROBLEMS

CORRECTIONS

No AC Output

Unit is not properly connected to utility power

Connect unit to utility power.

(All Indicator Lights are OFF)

Operating Mode Switch is set to “OFF” and AC input

Set Operating Mode Switch to “AUTO/REMOTE” or “CHARGE ONLY”.

is present.

This is normal when the Operating Mode Switch is set to

No correction is required. AC output will return when AC input 

“CHARGE ONLY” and AC input is absent.

returns. Set Operating Mode Switch to “AUTO/REMOTE” if you
require AC output.

Circuit breaker is tripped.

Reset circuit breaker.

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

battery damage). The problem may be with connected

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE” or

auxiliary chargers, if any, or with the unit’s charger.

“CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Unit has shut down due to excessive battery discharge.

Use an auxiliary charger* to raise battery voltage. Check external
battery connections and fuse. Unit automatically resets when
condition is cleared.

Unit has shut down due to overload.

Reduce load. Reset by moving Operating Mode Switch to “OFF”.
Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY”.

Battery Not Recharging

Connected batteries are dead.

Check and replace old batteries.

(AC Input Present)

Battery fuse* is blown.

Check and replace fuse.*

Battery cabling* is loose.

Check and tighten or replace cabling.*

Unit has shut down due to battery overcharge (preventing

Disconnect any auxiliary chargers. Reset by moving Operating Mode

battery damage). The problem may be with connected

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE” or

auxiliary chargers, if any, or with the unit’s charger.

or “CHARGE ONLY.” If unit remains in shutdown mode after several
attempts to reset, contact Tripp Lite Customer Service for assistance.

Input circuit breaker is tripped.

Reset circuit breaker.

All Three “BATT VOLT/CHRG CURR”

Battery is excessively discharged. Unit will shut down to

Use an auxiliary charger* to raise battery voltage. Check external

LEDs are slowly flashing (½ second 

prevent battery damage.

battery connections and fuse. Unit automatically resets when

flashes) with Operating Mode Switch in 

condition is cleared.

the “AUTO/REMOTE” position.

All Three “BATT VOLT/CHRG CURR”

Battery is overcharged. Unit will shut down to prevent

Disconnect any auxiliary chargers. Reset by moving Operating Mode

LEDs are rapidly flashing (¼ second 

battery damage. The problem may be with connected auxiliary

Switch to “OFF”. Wait 1 minute and switch to “AUTO/REMOTE.”

flashes) with Operating Mode Switch in 

chargers, if any, or with the unit’s charger.

If unit remains in shutdown mode after several attempts to reset,

the “AUTO/REMOTE” position.

contact Tripp Lite Customer Service for assistance.

Red “LOW” Battery Indicator Light is

Battery voltage is low. Unit has shut down

If AC power (utility- or generator-supplied) is present, the unit will

flashing with Operating Mode Switch in the 

to protect battery from damage.

automatically reset itself and start recharging connected batteries.

”AUTO/REMOTE” position.

However, if an external charger is used to recharge the batteries,
you will need to manually reset the unit by moving the Operating
Mode Switch to “OFF” for two seconds then returning it to
“AUTO/REMOTE”.

False reading due to undersized or

Use sufficient size DC cable sufficiently connected to 

insufficiently connected DC cabling.

Inverter/Charger.

Red “LOAD” Operation

Inverter is overloaded. Unit will automatically shut down

Reduce load. Reset by moving Operating Mode Switch to “OFF”.

Indicator Light flashing

after 5 seconds.

Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY”.

* User-supplied.

Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service at (773) 869-1234
before returning your unit for service.

200605181 RV Series Inverter-Charger Owner’s Manual.qxd  8/24/2006  2:35 PM  Page 13

Содержание PowerVerter RV Series

Страница 1: ...n Automatic Overload Protection Ideal Output for All Loads Frequency Controlled Output Automatic Load Switching Balanced Load Sharing Better for Your Batteries Faster Battery Recharge High Amp 3 Stage...

Страница 2: ...the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES...

Страница 3: ...ionary application in a dead air compartment Ideally any compartment would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batt...

Страница 4: ...ction for instructions Resettable Circuit Breaker protect your Inverter Charger against damage due to charger failure See Operation section for resetting instructions Remote Control Module Connector a...

Страница 5: ...ell at a glance a wide variety of oper ating details LINE Green LED If the operating mode switch is set to AUTO REMOTE this light will ILLUMI NATE CONTINUOUSLY when your connected equipment is receivi...

Страница 6: ...witch to OFF or DC OFF and remove some of the connected electrical load ie turn off some of the AC devices drawing power which may have caused the overload of the unit Wait one minute then switch oper...

Страница 7: ...ying its full AC power rating to its connected heavy electrical loads at the same time as this high charging occurs the AC input circuit breaker could trip resulting in the complete shut off of pass t...

Страница 8: ...to increase the minimum load that will be detected causing the inverter to stay off until the new minimum load is reached Note the factory setting for the dial is fully clockwise However based on the...

Страница 9: ...attery voltage 12 to determine the DC amps required STEP 3 Estimate Battery Amp Hours Required for operation unsupported by the alternator Multiply the DC amps required from step 2 above by the number...

Страница 10: ...ting the control panel of the Inverter Charger should face up All Models Except 750 1250 Models Note When operating an RV2012UL marine model in a marine application refer to the accompanying marine ow...

Страница 11: ...vehicles the Inverter Charger will be connected to one or more dedicated auxiliary house batteries which are isolated from the drive system to prevent possible draining of the main battery 12 Volt In...

Страница 12: ...ut power and WILL NOT provide 240V output even if it is connected to inputs from a split 240V service when in inverter mode When the Inverter Charger is receiving AC power it can supply connected load...

Страница 13: ...act Tripp Lite Customer Service for assistance Unit has shut down due to excessive battery discharge Use an auxiliary charger to raise battery voltage Check external battery connections and fuse Unit...

Страница 14: ...t Niveaux de protection de qualit sup rieure Protection ISOBAR int gr e contre les surtensions Protection automatique de surcharge Sortie id ale pour toutes les charges Sortie fr quence contr l e Comm...

Страница 15: ...T MARCHANDE OU DE CONFORMIT UN BESOIN PARTICULIER Certains tats ne permettent pas la limitation ou l exclusion de garanties implicites en cons quence les limitations ou exclusions ci dessus pourraient...

Страница 16: ...sans circulation d air Id alement un compartiment devrait avoir un ventilation d air ext rieur La connexion finale de la batterie peut causer des tincelles Toujours observer la bonne polarit en connec...

Страница 17: ...on tre les dommages dus une panne de chargeur Voir la section Fonctionnement pour les directives de r enclenchement Connecteurde module de commande distance permet la surveillance et le commande l aid...

Страница 18: ...voir d un coup d il de nombreux d tails de fonctionnement DEL vert de LIGNE Si le commutateur de mode fonctionnement est sur AUTO REMOTE cette lumi re sera ALLUM E CONTINUELLE MENT quand votre quipeme...

Страница 19: ...ment suite Position pour r armer votre chargeur onduleur pour restaurer l alimentation CA Votre chargeur onduleur peut cesser de fournir une alimentation CA ou une alimentation de charge CC de fa on s...

Страница 20: ...ect e est aliment e en CA plein r gime par votre unit et qu en m me temps cette charge lev e survient le disjoncteur d entr e CA peut sauter entra nant l arr t complet de l alimentation du secteur Pou...

Страница 21: ...sens antihoraire pour augmenter la charge minimale qui sera d tect entra nant la mise l arr t l onduleur jusqu ce que la nouvelle charge minimale soit atteinte Remarque Le r glage en usine est la rota...

Страница 22: ...l intensit CC requise TAPE 3 Estimation des A h de batterie requis pour un fonctionnement non support par l alternateur Multipliez l intensit requise d apr s l tape 2 ci dessus par le nombre estim d...

Страница 23: ...guration Pour le montage vertical le panneau de con tr le du circuit inverseur chargeur doit faire face au haut Tous les Mod les l exception des Mod les 750 et 1250 Note En faisant fonctionner le mod...

Страница 24: ...me lectrique de votre v hicule Dans la plupart des v hicules le chargeur onduleur sera connect l une ou plusieurs des batteries auxiliaires stationnaires d di es qui sont isol es du syst me de propuls...

Страница 25: ...ise la terre verte 1 Sortie Connectez les fils sortants aux bornes vivante noire neutre blanche et mise la terre verte 1 Replacer le couvercle et serrer les vis Si le tube protecteur entrant ne contie...

Страница 26: ...us garantie joindre une copie de votre facture Renvoyer le chargeur onduleur pour r paration par un transporteur assur l adresse que vous a donn le technicien de service de Tripp Lite C est la cause l...

Страница 27: ...en mode d arr t apr s plusieurs tentatives de r armement communiquez avec le service la client le de Tripp Lite pour de l aide Le disjoncteur du circuit a saut R armer le disjoncteur Les trois DEL BA...

Страница 28: ...200605181 93 2556 1111 W 35th Street Chicago IL 60609 USA Support la client le 773 869 1234 www tripplite com...

Страница 29: ...3000 OverPower Peak Surge Power 1125 1875 3000 3000 4500 DoubleBoost PeakSurgePower 1500 2500 4000 4000 6000 Maximum Output AC Current 6 3 A 10 4 A 16 7 A 16 7 A 25 A Continuous UL Recognized DC Fuse...

Страница 30: ...25 A 140 A 35 A Courant d entr e CA 8 2 A 11 A 20 A 21 A 25 A FONCTIONNEMENT DE LA LIGNE CA Sp cifications courantes pour tous les mod les Fr quence d entr e nominale 60 Hz 10 Tension d entr e maximal...

Отзывы: