12R

To avoid overloading your Inverter/Charger, match the power requirements of the equipment you plan to run at any one time (add their total
watts) with the output wattage capacity of your Inverter/Charger model (see Specifications). Do not confuse “continuous” wattage with
“peak” wattage ratings. Most electric motors require extra power at start-up (“peak wattage”) than required to run continuously after start-
up, sometimes over 100% more. Some motors, such as in refrigerators and pumps, start and stop intermittently according to demand, requir-
ing “peak wattage” at multiple, unpredictable times during operation. DoubleBoost

Feature: Tripp Lite Inverter/Chargers deliver up to twice

their nameplate rated wattage for up to 10 seconds,* providing the extra power needed to cold start heavy-duty tools and equipment.
OverPower

Feature: Tripp Lite Inverter/Chargers deliver up to 150% of their name-plate rated wattage for up to 1 hour,* providing plenty

of reserve power to reliably support tools and equipment longer.

* Actual duration depends on model, battery age, battery charge level and ambient temperature.

Warning! Consult a qualified electrician and follow all applicable electrical codes and requirements for
hardwire connection. Disconnect both DC input and AC utility supply before attempting hardwiring. Use wire
type THHN or equivalent with minimum temperature rating of 90°C.

Connection for Models with Hardwire Terminals

Output Connection Requirement: UL requires that the output terminals of all hard-
wire Inverter/Charger models must be connected to UL-listed GFCI receptacles 
(required receptacle manufacturer/model series: Hubbell GF8300 or
Leviton 6598).

Single Input/Output Models

Input:

Connect incoming wires to the hot (brown)      , neutral (blue)      

and ground* (green) terminals    .

Output:

Connect outgoing wires to the hot (black) 

, neutral (white)      

and ground* (green) terminals    .

Replace cover plate and tighten screws.* If the incoming conduit only contains two wires (hot and neutral), the incoming conduit must be bonded to the main ground lug on the unit. In any case,
the incoming conduit must be bonded to earth or vehicle ground, and the incoming conduit must be bonded to the outgoing conduit.

Dual Input/Output Models

Select models provide higher bypass power capacity by enabling connection of two separate
AC input sources. These two sources can be either two 120V legs split from a single 240V
service (with opposite phase on each 120V leg) or two different 120V sources. The
Inverter/Charger will only supply 120V output power and WILL NOT provide 240V output
even if it is connected to inputs from a split 240V service when in inverter mode. When the
Inverter/Charger is receiving AC power, it can supply connected loads with up to 30 amps
of power on each circuit**. When the Inverter/Charger is not receiving AC power, and has
switched to inverting DC battery power, it can supply connected loads with various amper-
age levels (see “Maximum Output AC Current” in Specifications section) on BOTH circuits.
Dual input/output models provide for either: a) dual-source inputs and outputs; b) single-
source input and output; or c) single-source input and dual-source outputs (with AC OUT
2 power only available in invert mode). Connect user-supplied wire and conduit to the con-
nections as follows: 

Input:

Connect incoming wires to hot (black for AC IN 1, black for AC IN 2), neutral

(white for AC IN 1, white for AC IN 2) and ground (green/yellow) wires. 

Output:

Connect outgoing wires to hot (black for AC OUT 1, black for AC OUT 2), neutral

(white for AC OUT 1, white for AC OUT 2) and ground (green/yellow) wires. 

* Single-Source or Dual-Source Input/Output Connection: As well as supplying power to connected loads, AC IN 1 also provides power to the battery charger. If you connect a large load to AC OUT 1,
you should select a more limiting battery charger setting (see “Select Battery Charger-Limiting Points”) or you may experience continual nuisance tripping of the electrical service (source) circuit
breaker which supplies AC IN 1. The Inverter/Charger will only measure the current at AC OUT 1 to automatically limit the charger rate. AC IN 2 input current is passed through to AC OUT 2 with-
out measurement. Single-Source Input/Dual-Source Output Connection: You may connect AC IN 1 and AC IN 2 to a single source to provide power to AC OUT 1 and AC OUT 2. However, the loads connected to
AC OUT 2 will not be measured for the purpose of automatic charger limitation. This could result in occasional tripping of the electrical service (source) circuit breaker. If this occurs, reduce the load on AC OUT
2 until nuisance tripping stops.

** Limited by user-supplied circuit breakers.

1

2

3

4

5

AC Input/Output Connection

HOT    IN

NEUTRAL    IN

GROUND    IN

GROUND    OUT

HOT    OUT

“FOR USE WITH COPPER WIRE ONLY”

NEUTRAL    OUT

2

3

1

4

5

Note: Ground Bond Connection, Supplied

AC IN 1

AC IN 2

AC OUT 2

AC OUT 1

1

Dual-Source Input/Output*

• AC IN 1 will only provide line power to AC OUT 1.
• AC IN 2 will only provide line power to AC OUT 2.
• Inverted battery power is supplied to both AC OUT 1 and AC OUT 2.

Single-Source Input/Output*

• If you only have a single 120V AC input source, you must 

connect it to AC IN 1.

• If you only have a single output circuit, you must connect it to

AC OUT 1

200605181 RV Series Inverter-Charger Owner’s Manual.qxd  8/24/2006  2:35 PM  Page 12

Содержание PowerVerter RV Series

Страница 1: ...n Automatic Overload Protection Ideal Output for All Loads Frequency Controlled Output Automatic Load Switching Balanced Load Sharing Better for Your Batteries Faster Battery Recharge High Amp 3 Stage...

Страница 2: ...the aforesaid limitation s or exclusion s may not apply to the purchaser EXCEPT AS PROVIDED ABOVE IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT INDIRECT SPECIAL INCIDENTAL OR CONSEQUENTIAL DAMAGES...

Страница 3: ...ionary application in a dead air compartment Ideally any compartment would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batt...

Страница 4: ...ction for instructions Resettable Circuit Breaker protect your Inverter Charger against damage due to charger failure See Operation section for resetting instructions Remote Control Module Connector a...

Страница 5: ...ell at a glance a wide variety of oper ating details LINE Green LED If the operating mode switch is set to AUTO REMOTE this light will ILLUMI NATE CONTINUOUSLY when your connected equipment is receivi...

Страница 6: ...witch to OFF or DC OFF and remove some of the connected electrical load ie turn off some of the AC devices drawing power which may have caused the overload of the unit Wait one minute then switch oper...

Страница 7: ...ying its full AC power rating to its connected heavy electrical loads at the same time as this high charging occurs the AC input circuit breaker could trip resulting in the complete shut off of pass t...

Страница 8: ...to increase the minimum load that will be detected causing the inverter to stay off until the new minimum load is reached Note the factory setting for the dial is fully clockwise However based on the...

Страница 9: ...attery voltage 12 to determine the DC amps required STEP 3 Estimate Battery Amp Hours Required for operation unsupported by the alternator Multiply the DC amps required from step 2 above by the number...

Страница 10: ...ting the control panel of the Inverter Charger should face up All Models Except 750 1250 Models Note When operating an RV2012UL marine model in a marine application refer to the accompanying marine ow...

Страница 11: ...vehicles the Inverter Charger will be connected to one or more dedicated auxiliary house batteries which are isolated from the drive system to prevent possible draining of the main battery 12 Volt In...

Страница 12: ...ut power and WILL NOT provide 240V output even if it is connected to inputs from a split 240V service when in inverter mode When the Inverter Charger is receiving AC power it can supply connected load...

Страница 13: ...act Tripp Lite Customer Service for assistance Unit has shut down due to excessive battery discharge Use an auxiliary charger to raise battery voltage Check external battery connections and fuse Unit...

Страница 14: ...t Niveaux de protection de qualit sup rieure Protection ISOBAR int gr e contre les surtensions Protection automatique de surcharge Sortie id ale pour toutes les charges Sortie fr quence contr l e Comm...

Страница 15: ...T MARCHANDE OU DE CONFORMIT UN BESOIN PARTICULIER Certains tats ne permettent pas la limitation ou l exclusion de garanties implicites en cons quence les limitations ou exclusions ci dessus pourraient...

Страница 16: ...sans circulation d air Id alement un compartiment devrait avoir un ventilation d air ext rieur La connexion finale de la batterie peut causer des tincelles Toujours observer la bonne polarit en connec...

Страница 17: ...on tre les dommages dus une panne de chargeur Voir la section Fonctionnement pour les directives de r enclenchement Connecteurde module de commande distance permet la surveillance et le commande l aid...

Страница 18: ...voir d un coup d il de nombreux d tails de fonctionnement DEL vert de LIGNE Si le commutateur de mode fonctionnement est sur AUTO REMOTE cette lumi re sera ALLUM E CONTINUELLE MENT quand votre quipeme...

Страница 19: ...ment suite Position pour r armer votre chargeur onduleur pour restaurer l alimentation CA Votre chargeur onduleur peut cesser de fournir une alimentation CA ou une alimentation de charge CC de fa on s...

Страница 20: ...ect e est aliment e en CA plein r gime par votre unit et qu en m me temps cette charge lev e survient le disjoncteur d entr e CA peut sauter entra nant l arr t complet de l alimentation du secteur Pou...

Страница 21: ...sens antihoraire pour augmenter la charge minimale qui sera d tect entra nant la mise l arr t l onduleur jusqu ce que la nouvelle charge minimale soit atteinte Remarque Le r glage en usine est la rota...

Страница 22: ...l intensit CC requise TAPE 3 Estimation des A h de batterie requis pour un fonctionnement non support par l alternateur Multipliez l intensit requise d apr s l tape 2 ci dessus par le nombre estim d...

Страница 23: ...guration Pour le montage vertical le panneau de con tr le du circuit inverseur chargeur doit faire face au haut Tous les Mod les l exception des Mod les 750 et 1250 Note En faisant fonctionner le mod...

Страница 24: ...me lectrique de votre v hicule Dans la plupart des v hicules le chargeur onduleur sera connect l une ou plusieurs des batteries auxiliaires stationnaires d di es qui sont isol es du syst me de propuls...

Страница 25: ...ise la terre verte 1 Sortie Connectez les fils sortants aux bornes vivante noire neutre blanche et mise la terre verte 1 Replacer le couvercle et serrer les vis Si le tube protecteur entrant ne contie...

Страница 26: ...us garantie joindre une copie de votre facture Renvoyer le chargeur onduleur pour r paration par un transporteur assur l adresse que vous a donn le technicien de service de Tripp Lite C est la cause l...

Страница 27: ...en mode d arr t apr s plusieurs tentatives de r armement communiquez avec le service la client le de Tripp Lite pour de l aide Le disjoncteur du circuit a saut R armer le disjoncteur Les trois DEL BA...

Страница 28: ...200605181 93 2556 1111 W 35th Street Chicago IL 60609 USA Support la client le 773 869 1234 www tripplite com...

Страница 29: ...3000 OverPower Peak Surge Power 1125 1875 3000 3000 4500 DoubleBoost PeakSurgePower 1500 2500 4000 4000 6000 Maximum Output AC Current 6 3 A 10 4 A 16 7 A 16 7 A 25 A Continuous UL Recognized DC Fuse...

Страница 30: ...25 A 140 A 35 A Courant d entr e CA 8 2 A 11 A 20 A 21 A 25 A FONCTIONNEMENT DE LA LIGNE CA Sp cifications courantes pour tous les mod les Fr quence d entr e nominale 60 Hz 10 Tension d entr e maximal...

Отзывы: