TMCM-1021 TMCL
™
Firmware Manual • Firmware Version V1.42 | Document Revision V1.10 • 2018-JAN-09
32 / 109
3.7.8
RSAP (Restore Axis Parameter)
With this command the contents of an axis parameter can be restored from the EEPROM. By default, all
axis parameters are automatically restored after power up. An axis parameter that has been changed
before can be reset to the stored value by this instruction.
Info
For a table with parameters and values which can be used together with this
command please refer to section
Internal function:
The axis parameter specified by the type and bank number will be restored from the
EEPROM.
Related commands:
SAP, AAP, GAP, RSAP.
Mnemonic:
RSAP <parameter number>, <bank>
Binary Representation
Instruction
Type
Motor/Bank
Value
8
see chapter
0
0 (don’t care)
Reply in Direct Mode
Status
Value
100 - OK
0 (don’t care)
Example
Restore axis parameter #6.
Mnemonic:
RSAP 8, 6.
Binary Form of RSAP 8, 6
Field
Value
Target address
01
h
Instruction number
08
h
Type
06
h
Motor/Bank
00
h
Value (Byte 3)
00
h
Value (Byte 2)
00
h
Value (Byte 1)
00
h
Value (Byte 0)
00
h
Checksum
0A
h