Startup
RT-SVX34F-EN
63
Table 39. Supply fan performance
—
22.9-29.1 ton (I-P) — 50 Hz
SCF
M
Static Pressure (in. wg)
0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6670 283 0.80 351 1.18 410 1.58 469 2.08 524 2.63 573 3.20 617 3.78 659 4.37 696 4.96
7085 291 0.90 358 1.31 413 1.70 469 2.21 524 2.78 574 3.37 619 3.98 660 4.59 698 5.22
7500 299 1.02 364 1.43 418 1.86 472 2.35 524 2.92 574 3.55 619 4.18 661 4.82 699 5.46
7915 306 1.14 371 1.58 425 2.05 475 2.51 524 3.08 574 3.72 620 4.38 661 5.04 701 5.73
8330 313 1.27 378 1.75 433 2.25 478 2.69 527 3.26 574 3.89 620 4.58 662 5.27 702 5.99
8745 321 1.42 386 1.93 439 2.43 484 2.92 530 3.45 574 4.08 620 4.79 663 5.51 702 6.24
9160 330 1.58 394 2.12 445 2.62 492 3.18 533 3.67 577 4.30 620 4.99 664 5.74 703 6.50
9575 339 1.76 403 2.32 452 2.84 499 3.44 538 3.93 580 4.53 622 5.22 663 5.96 703 6.76
9990 349 1.95 411 2.54 459 3.08 505 3.68 545 4.24 583 4.80 624 5.49 663 6.21 703 7.02
10405 360 2.17 419 2.77 467 3.34 511 3.92 552 4.57 588 5.09 628 5.77 665 6.49 703 7.28
10820 371 2.41 426 3.00 475 3.62 518 4.20 560 4.90 595 5.46 631 6.07 668 6.80 705 7.59
11235 383 2.66 434 3.25 483 3.90 525 4.50 566 5.19 603 5.85 634 6.41 671 7.13 707 7.90
11650 394 2.93 441 3.51 492 4.21 532 4.83 572 5.51 610 6.25 642 6.84 675 7.50 710 8.26
12065 405 3.23 449 3.79 500 4.53 540 5.18 578 5.83 616 6.61 649 7.30 680 7.90 714 8.67
SCF
M
Static Pressure (in. wg)
2.50
2.75
3.00
RPM BHP RPM BHP RPM BHP
6670 733 5.60 767 6.23 800 6.88
7085 735 5.86 769 6.52 802 7.18
7500 736 6.13 771 6.82 803 7.49
7915 737 6.40 772 7.10 806 7.83
8330 739 6.70 773 7.41 807 8.16
8745 740 6.99 775 7.73 808 8.49
9160 740 7.25 776 8.06 809 8.83
9575 740 7.54 777 8.38 810 9.17
9990 741 7.83 776 8.65 811 9.51
10405 742 8.14 777 8.99 812 9.86
10820 741 8.41 777 9.31 812 10.21
11235 742 8.74 778 9.63 812 10.55
11650 745 9.11 778 9.96 812 10.89
12065 747 9.47 779 10.34 811 11.24
Notes:
1.
Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system
external static must be added to appropriate component static pressure drops, (evaporator coil, filters, optional
economizer, optional heating system, optional roof curb).
2.
The pressure drops from the supply fan to the space should not exceed 2.25” (558.8 Pa) positive.
3.
Maximum air flow 23 ton (80 kW) is 4756 L/s, 25 ton is 5190 L/s, 29 ton is 5663 L/s
4.
Maximum motor kW for 23 ton unit is 7.5 (10 hp), 25 ton is 7.5 kW (10 hp), 29 ton is 11.2 kW (15 hp).