Installation Electrical
RT-SVX34F-EN
31
Figure 20.
Typical field wiring requirements for traditional VAV control options
Customer
Changeover
for VAV Htg
(MOD GAS
ONLY
*VAV Mode input: RTRM J6-2 to RTRM J6-4
If the unit does not have a Mode (Off, Auto) input from another source,
the following default applies: Short from J6-2 to J6-4 = AUTO mode,
Open from J6-2 to J6-4 = OFF mode.
LTB6
Space
Humidity
Sensor
Space
Humidistat
Figure 21.
RTRM zone sensor/thermostat connections
PROGRAMMABLE
ZSM INPUTS
CV/SZ VAV/VAV
CONVENTIONAL
THERMOSTAT (CV ONLY)
MECHANICAL
ZSM INPUTS
CONVENTIONAL
THERMOSTAT
INPUTS