Installation Electrical
26
RT-SVX34F-EN
Table 8.
Electrical service sizing data — electric heat
module (electric heat only) — 60 Hz
Models: TE(D,H,F,R) 330—600 Electric Heat FLA
KW Heater
Nominal
Unit Size
(Tons)
Nominal
Unit
Voltage
36
54
72
90
108
FLA
FLA
FLA
FLA
FLA
27½-35
208
74.9
112.4
—
—
—
230
86.6
129.9
—
—
—
460
43.3
65.0
86.6
108.3
—
575
—
52.0
69.3
86.6
—
40- 50
208
—
112.4
—
—
—
230
—
129.9
—
—
—
460
—
65.0
86.6
108.3
129.9
575
—
52.0
69.3
86.6
103.9
Note:
All FLA in this table are based on heater operating at 208, 240, 480,
and 600 volts.
Table 9.
Electrical service sizing data — crankcase
heaters (heating mode only) — 60Hz
Nominal
Unit Size (Tons)
FLA Add Unit Voltage
200
230
460
575
27½ - 35
1
1
1
1
40, 50
2
2
1
1
Table 10.
Electrical service sizing data — 50Hz
Model
Electrical
Characteristics
Compressor
Fan Motors
Supply
Condenser
1
Exhaust
No/Ton
RLA
(Ea.)
LRA
(Ea.) HP(kW) FLA
No. HP(kW)
FLA
(Ea.)
50% 100%
4
HP
(kW)
FLA
(Ea.)
No.
TC/TE/YC*275
380-415/50/3
1/10, 1/11 21.0/23.0 147/ 158 7.5 (5.6)
13.6/
14.1
3
.75 (.56)
4.4
1
2
0.75
(0.56)
1.7
10 (6.8)
16.0/
15.5
TC/TE/YC*305
380-415/50/3
2/11
23.0
158
7.5 (5.6)
13.6/
14.1
3
0.75
(0.56)
4.4
1
2
0.75
(0.56)
1.7
10 (6.8)
16.0/
15.5
TC/TE/YC*350
380-415/50/3
1/11, 1/12 23.0/27.5 158/ 197 7.5 (5.6)
13.6/
14.1
3
0.75
(0.56)
4.4
1
2
0.75
(0.56)
1.7
10 (6.8)
16.0/
15.5
15 (10.5)
24.0/
26.0
TC/TE/YC*400
380-415/50/3
1/11, 1/17 23.0/34.0 158/ 215 10 (6.8)
16.0/
15.5
4
0.75
(0.56)
4.4
1
2
1.0
(0.75)
2.5
15 (10.5) 24.0/
26.0
TC/TE/YC*500
380-415/50/3
2/11, 1/12 23.0/27.5 158/ 197 10 (6.8)
16.0/
15.5
4
0.75
(0.56)
4.4
1
2
1.0
(0.75)
2.5
15 (10.5)
24.0/
26.0
20 (12.8) 29.0/
28.0
Notes:
1.
All condenser fan motors are single phase.
2.
All customer wiring and devices must be installed in accordance with local and national electrical codes.
3.
Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
4.
100% Power Exhaust is with or without Statitrac.