Configuration
CNT-SVX04A-EN
77
Table 41
Coil temperature definition table
Note 1:
Table 42 on page 78 identifies the logic for determining the main coil temperature for main coil changeover applications.
Cooling source
Heating source
Main coil
Auxiliary coil Description
None
None
Hydronic (changeover)
Hydronic, dedicated coil heating
Hot
NA
2-pipe heat only
Steam
Hot
NA
2-pipe steam heat only
Compressor
Electric
NA
NA
Electric heat only
(Force Flo)
Hydronic (chan dedicated hydronic
Hydronic (chan electric
Hydronic, main
coil changeover
None
Hydronic, main coil changeover
(Note 1)
NA
2-pipe changeover
Dedicated hydronic
Steam
Compressor
Electric
Hydronic coil chan auxiliary coil
heating
(Note 1)
Hot
4-pipe changeover
Hydronic (chan electric
(Note 1)
NA
2-pipe changeover w/ electric heat
Hydronic, main
coil cooling
None
Cold
NA
2-pipe cooling only
Hydronic (changeover)
Hydronic, dedicated coil heating
Cold
Hot
4-pipe
Steam
Cold
Hot
4-pipe (steam heat)
Compressor
Electric
Cold
NA
2-pipe cool only w/ electric heat
Hydronic (chan dedicated hydronic
Hydronic (chan electric
DX
None
Hydronic (changeover)
Dedicated hydronic
NA
Hot
DX unit vent w/ hot water heat
Steam
NA
Hot
DX unit vent w/ hot water heat
Compressor
Electric
NA
NA
DX unit vent w/ electric heat
Hydronic (chan dedicated hydronic
Hydronic (chan electric