Appendix
CNT-SVX04A-EN
105
Data lists
Table 71 provides an input/output listing for the Tracer ZN.520 zone controller.
Table 72 provides the configuration properties for the zone controller. The
content of the lists conforms to both the LonMark Space Comfort Controller
Functional Profile 85.00 and the LonMark node object.
Table 71
Input/output listing
1
Input
SNVT type
Output
SNVT type
nviRequest
SNVT_obj_request
nvoStatus
SNVT_obj_status
nviSpaceTemp
SNVT_temp_p
nvoFileDirectory
SNVT_address
nviSetpoint
SNVT_temp_p
nvoSpaceTemp
SNVT_temp_p
nviSetptOffset
SNVT_temp_p
nvoUnitStatus
SNVT_hvac_status
nviOccSchedule
SNVT_tod_event
nvoEffectSetpt
SNVT_temp_p
nviOccManCmd
SNVT_occupancy
nvoEffectOccup
SNVT_occupancy
nviOccSensor
SNVT_occupancy
nvoHeatCool
SNVT_hvac_mode
nviApplicMode
SNVT_hvac_mode
nvoSetpoint
SNVT_temp_p
nviHeatCool
SNVT_hvac_mode
nvoDischAirTemp
SNVT_temp_p
nviFanSpeedCmd
SNVT_switch
nvoTerminalLoad
SNVT_lev_percent
nviComprEnable
SNVT_switch
nvoSpaceRH
SNVT_lev_percent
nviAuxHeatEnable
SNVT_switch
nvoOutdoorTemp
SNVT_temp_p
nviValveOverride
SNVT_hvac_overid
nvoSpaceCO2
SNVT_ppm
nviEmergOverride
SNVT_hvac_emerg
nvoEnterWaterTemp
SNVT_temp_p
nviSourceTemp
SNVT_temp_p
nviSpaceRH
SNVT_lev_percent
Note
1
:
LonMark certification pending
Table 72
Configuration properties
1
Configuration property
SNVT type
SCPT reference
Description
nciSndHrtBt
SNVT_time_sec
SCPTmaxSendTime (49)
Send heartbeat
nciSetpoints
SNVT_temp_setpt
SCPTsetPnts (60)
Occupancy temperature setpoints
nciUnitType
SNVT_hvac_type
SCPThvacUnitType (169)
Unit type
nciMinOutTm
SNVT_time_sec
SCPTminSendTime (52)
Minimum send time
nciRcvHrtBt
SNVT_time_sec
SCPTmaxRcvTime (48)
Receive heartbeat
nciLocation
SNVT_str_asc
SCPTlocation (17)
Location label
nciBypassTime
SNVT_time_min
SCPTbypassTime (34)
Local bypass time
nciSpaceRHSetpt
SNVT_lev_percent
Space RH setpoint
nciOAMinPos
SNVT_lev_percent
Minimum outside air position during
occupied mode